SA I4D6 Fire hydrants and water supplies
SA Part I4 Bulk grain storage facilities
Delete clause I4D6 and insert SA I4D6 as follows:
(1) A bulk grain storage facility need not provide an on-site fire hydrant system in accordance with E1D2, where—
street hydrants are available adjacent to the site that can supply water at not less than 5 litres per second; or
a water supply system comprising single or multiple on-site water storage tanks with connections for use by the fire brigade and complying with the requirements of AS 2419.1 for water supplies and water storage is provided, except—
in lieu of a 4 hour water supply, an on0site water storage tank containing not less than 25,000 litres is provided within 90 m of a dry booster connection Figure SA I4D6; and
one dry riser is provided for each cell type silo, located in the middle of the longest side of the bulk grain storage facility and within 4 m of a required exit; and
all areas to be protected are within 60 m of a riser outlet, measured around obstacles; and
metal or high pressure plastic pipe can used for the dry riser; and
all pipes, valves and fittings for water storage tanks and connections must comply with section 5 and sections 8.2, 8.3, 8.6 and 8.7 of AS 2419.1 as relevant.
(2) A dam may be regarded as a water storage tank if it complies with the requirements of section 5 of AS 2419.1 and the water level is maintained above the top of the highest fire brigade suction point at all times.
(3) A hardstand area and vehicular approach from the site entrance, suitable for use by the fire brigade, must be provided adjacent to each water storage tank provided under (1)(b).
Insert SA figure (I4D6) I4D6 as follows:
SA Figure I4D6: Location of hydrants, tanks, booster connections and dry risers
Other states and territories
- WA Delete clause I4D6 and insert WA I4D6 as follows: (1) Artificial lighting must be provided along the external path of…
- NSW Delete clause I4D6 and insert NSW I4D6 as follows: If a room or area is not separated from the remainder of a…
- TAS Delete clause I4D6 and insert TAS I4D6 as follows: Where offensive material or trade waste is stored, a separate area…