Table · NCC 2025 Volume One

Table F1D11 Subfloor openings and ground clearance

Part F1 Water management

Open Table F1D11 on NCC Online ↗
Climatic zone (see Figure F1D11)Minimum aggregate subfloor ventilation openings without a membrane (mm2/m of wall)Minimum aggregate subfloor ventilation openings having the ground sealed with an impervious membrane (mm2/m of wall)Minimum ground clearance height where termite inspection or management system is not required (mm)Minimum ground clearance height where termite inspection is required (mm) Note 1
A20001000150400
B40002000150400
C60003000150400

Table Notes

400 mm clearance required only where termite management systems are installed that need to be inspected (see B1D4).

On sloping sites, the 400 mm clearance required by (1) may be reduced to 150 mm within 2 m of external walls.

In situations where openings in external walls and internal subfloor walls are not able to be provided, additional measures must be provided to ensure that the overall level of ventilation of the subfloor space is maintained.

Additional measures referred to in (3) may include measures similar to those in F1D11(5), such as providing durability class timbers, or having the ground sealed in the subfloor space with an impervious membrane.

Table for F1D11 Subfloor ventilation

New in NCC 2025. No Table F1D11 in NCC 2022 Volume One; it may have moved or been renumbered.