Table · NCC 2025 Volume One

Table F6V2 Maximum carbon monoxide exposure for carparks

Part F6 Light and ventilation

Open Table F6V2 on NCC Online ↗
Concentration (ppm)Total exposure duration per day
100Not to be exceeded
9015 minutes
601 hour
308 hours

Table Notes

Various government work health and safety regulations specify workplace exposure limits for airborne contaminants in the workplace.

Table for F6V2 Verification of suitable indoor air quality for carparks

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table F6V2.