Table · NCC 2025 Volume One

Table J3D12a Constant for Solar Heat Gain (CSHGC) — climate zones 1 to 7

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D12a on NCC Online ↗
% Ventilation opening area per m2Climate zone 1Climate zone 2Climate zone 3Climate zone 4Climate zone 5Climate zone 6Climate zone 7
5% to <10%0.01910.02450.05470.05060.06740.14720.0930
10% to <15%0.02370.05320.07450.09460.11110.29690.2405
15% to <20%0.02940.07000.08610.12030.13670.38450.3267
20% to 90%0.03640.08190.09430.13850.15480.44660.3879

Table Notes

The ventilation opening area is the total area of each ventilation opening divided by the floor area of the storey, including any mezzanine.

No window can have a design ventilation opening greater than 90% because the window frame will always obstruct some area of the opening.

Interpolation is allowed for values between those shown.

Table for J3D12 External summer glazing of a Class 4 part of a building

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D12a.

Defined terms used