Table · NCC 2025 Volume One
Table J3D7e Timber-framed pitched roof with horizontal ceiling — minimum R-Value for ceiling insulation: climate zone 2
Part J3 Elemental provisions for a Class 4 part of a building
| Roof ventilation | Reflective insulation under-roof | Under-roof insulation R-Value | SA ≤ 0.23 | SA > 0.23 to ≤ 0.32 | SA > 0.32 to ≤ 0.42 | SA > 0.42 to ≤ 0.53 | SA > 0.53 to ≤ 0.64 |
|---|---|---|---|---|---|---|---|
| Vented | Yes | Any | 2.5 | ||||
| No | 0 to < 0.5 | 2.5 | 3.0 | 3.0 | 3.5 | 3.5 | |
| ≥ 0.5 | 2.5 | ||||||
| Standard | Yes | Any | 2.5 | ||||
| No | 0 to < 0.5 | 3.0 | 3.0 | 3.5 | 4.0 | 4.0 | |
| ≥ 0.5 to < 1.0 | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 | ||
| ≥ 1.0 | 2.5 |
Table Notes
SA = solar absorptance.
A roof is considered ‘vented’ if it—
has one wind-driven roof ventilator per 50 m2 of ceiling area with gable, eave or ridge vents; or
has one powered roof ventilator per 200 m2 of ceiling area with gable, eave or ridge vents; or
is a tiled roof without sarking-type material at roof level.
If a roof is not ‘vented’, it is a ‘standard’ roof.
The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.
R-Values listed are for the labelled, declared R-Value of insulation.
Table for J3D7 Roofs and ceilings of a Class 4 part of a building
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D7e.