Table · NCC 2025 Volume One

Table J3D7f Timber-framed flat, skillion or cathedral roof — minimum R-Value for ceiling insulation: climate zone 2

Part J3 Elemental provisions for a Class 4 part of a building

Open Table J3D7f on NCC Online ↗
Reflective insulation under-roofSA ≤ 0.23SA > 0.23 to ≤ 0.32SA > 0.32 to ≤ 0.42SA > 0.42 to ≤ 0.53SA > 0.53 to ≤ 0.64
Yes2.52.52.52.52.5
No3.03.03.54.04.0

Table Notes

SA = solar absorptance.

The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for J3D7 Roofs and ceilings of a Class 4 part of a building

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J3D7f.

Defined terms used