Table J4D7 Floors – Minimum Total R-Value
| Location | Climate zone 1— upwards heat flow | Climate zones 2 and 3 — upwards and downwards heat flow | Climate zones 4, 5, 6 and 7 — downwards heat flow | Climate zone 8 — downwards heat flow |
|---|---|---|---|---|
| A floor without an in-slab heating or cooling system | 2.0 | 2.0 | 2.0 | 3.5 |
| A floor with an in-slab heating or cooling system | 3.25 | 3.25 | 3.25 | 4.75 |
Table Notes
For the purpose of calculating the Total R-Value of a floor, the sub-floor and soil R-Value must be calculated in accordance with Specification 39 or Section 3.5 of CIBSE Guide A.
Table for J4D7 Floors
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J4D7.