J4D6 Walls and glazing
Part J4 Building fabric · NCC 2019: J1.5
(1) The Total System U-Value of wall-glazing construction, including wall-glazing construction which wholly or partly forms the envelope internally, must not be greater than the values specified in Table J4D6a.
(2) The Total System U-Value of glazing, including display glazing, must not be greater than U5.8.
(3) The Total System U-Value of wall-glazing construction must be calculated in accordance with Specification 37.
(4) Wall components of a wall-glazing construction must achieve a minimum Total R-Value of—
where the wall is less than 80% of the area of the wall-glazing construction, R1.0; or
where the wall is 80% or more of the area of the wall-glazing construction, the value specified in Table J4D6b.
(5) The solar admittance of externally facing wall-glazing construction, excluding wall-glazing construction which is wholly internal, must not be greater than—
for a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, the values specified in Table J4D6c; and
for a Class 3 or 9c building or a Class 9a ward area, the values specified in Table J4D6d.
(6) The solar admittance of a wall-glazing construction must be calculated in accordance with Specification 37.
(7) The Total system SHGC of display glazing must not exceed the lesser of the following:
0.81 divided by the applicable shading factor specified in S37C7.
1.
Table J4D6a Maximum Total System U-Value of wall-glazing construction
Climate zone
Class 5, 6, 7, 8, 9b building or a Class 9a building other than a ward area
Class 3 or 9c building or a Class 9a ward area
1
1.6
1.1
2
1.9
1.6
3
1.7
1.2
4
1.7
1.3
5
1.9
1.6
6
1.8
1.6
7
1.7
1.2
8
2.0
1.1
Table J4D6b Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area
Climate zone
Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area
Class 3 or 9c building or Class 9a ward area
1
3.0
4.0
2
1.0
1.0
3
2.2
2.4
4
2.0
1.9
5
1.0
1.0
6
1.2
1.0
7
2.2
2.2
8
3.6
3.6
Table J4D6c Maximum wall-glazing construction solar admittance - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
Climate zone
Eastern aspect solar admittance
Northern aspect solar admittance
Southern aspect solar admittance
Western aspect solar admittance
1 to 7
0.10
0.09
0.11
0.09
8
0.10
0.10
0.20
0.10
Table J4D6d Maximum wall glazing construction solar admittance - Class 3 or 9c building or Class 9a ward area
Climate zone
Eastern aspect solar admittance
Northern aspect solar admittance
Southern aspect solar admittance
Western aspect solar admittance
All
0.06
0.06
0.06
0.06
Tables
- Table J4D6a Maximum Total System U-Value of wall-glazing construction
- Table J4D6b Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area
- Table J4D6c Maximum wall-glazing construction solar admittance - Class 5, 6, 7, 8 or 9b building or Class 9a building other than a ward area
- Table J4D6d Maximum wall glazing construction solar admittance - Class 3 or 9c building or Class 9a ward area
Changed since NCC 2022. See NCC 2022 Volume One J4D6, or show what changed.
(1) The Total System U-Value of wall-glazing construction, including wall-glazing construction which wholly or partly forms the envelope internally, must not be greater than — for a Class 2 common area, a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, U2.0; and for a Class 3 or 9c building or a Class 9a ward area — the values specified in climate zones 1, 3, 4, 6 or 7, U1.1; or in climate zones 2 or 5, U2.0; or in climate zone 8, U0.9. Table J4D6a. (2) The Total System U-Value of glazing, including display glazing glazing, must not be greater than U5.8. (3) The Total System … area of the wall-glazing construction, the value specified in Table J4D6a. J4D6b. (5) The solar admittance of externally facing wall-glazing construction, excluding … internal, must not be greater than — for a Class 2 common area, a Class 5, 6, 7, 8 or 9b building or a Class 9a building other than a ward area, the values specified in Table J4D6b; J4D6c; and for a Class 3 or 9c building or a Class 9a ward area, the values specified in Table J4D6c. J4D6d. (6) The solar admittance of a wall-glazing construction must be … (7) The Total system SHGC of display glazing must not be greater than exceed the lesser of the following: 0.81 divided by the applicable shading factor specified in S37C7. 1. Table J4D6a Maximum Total System U-Value of wall-glazing construction Climate zone Class 5, 6, 7, 8, 9b building or a Class 9a building other than a ward area Class 3 or 9c building or a Class 9a ward area 1 1.6 1.1 2 1.9 1.6 3 1.7 1.2 4 1.7 1.3 5 1.9 1.6 6 1.8 1.6 7 1.7 1.2 8 2.0 1.1 Table J4D6b Minimum wall Total R-Value - Wall area 80% or more of wall-glazing construction area Climate zone Class 2 common area, Class 5, 6, 7, 8 or 9b building or a … 3 or 9c building or Class 9a ward area 1 3.0 4.0 2 1.0 1.0 3 2.2 2.4 3.3 2 1.4 1.4 3 1.4 3.3 4 1.4 2.8 2.0 1.9 5 1.4 1.4 1.0 1.0 6 1.4 2.8 1.2 1.0 7 1.4 2.8 2.2 2.2 8 1.4 3.8 3.6 3.6 Table J4D6b J4D6c Maximum wall-glazing construction solar admittance - Class 2 common area, Class 5, 6, 7, 8 or 9b building or Class … admittance Southern aspect solar admittance Western aspect solar admittance 1 0.12 0.12 0.12 0.12 2 0.13 0.13 0.13 0.13 3 0.16 0.16 0.16 0.16 4 0.13 0.13 0.13 0.13 5 0.13 0.13 0.13 0.13 6 0.13 0.13 0.13 0.13 to 7 0.13 0.13 0.13 0.13 0.10 0.09 0.11 0.09 8 0.2 0.2 0.42 0.36 0.10 0.10 0.20 0.10 Table J4D6c J4D6d Maximum wall-glazing wall glazing construction solar admittance - Class 3 or 9c building or … solar admittance Southern aspect solar admittance Western aspect solar admittance 1 0.07 0.07 0.10 0.07 2 0.10 0.10 0.10 0.10 3 0.07 0.07 0.07 0.07 4 0.07 0.07 0.07 0.07 5 0.10 0.10 0.10 0.10 6 0.07 0.07 0.07 0.07 7 0.07 0.07 0.08 0.07 8 0.08 0.08 0.08 0.08 All 0.06 0.06 0.06 0.06
Removed words are struck through; added words are highlighted. Comparison of the text only.