Table · NCC 2025 Volume One
Table J6D8b Maximum pipework pressure drop – Non-distributive variable flow systems
Part J6 Air-conditioning and ventilation
| Nominal pipe diameter (mm) | Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m) | Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m) |
|---|---|---|
| Not more than 20 | 400 | 400 |
| 25 | 400 | 400 |
| 32 | 400 | 400 |
| 40 | 400 | 400 |
| 50 | 400 | 400 |
| 65 | 400 | 400 |
| 80 | 400 | 400 |
| 100 | 400 | 300 |
| 125 | 400 | 300 |
| 150 or more | 400 | 300 |
Table for J6D8 Pump systems
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table J6D8b.