J6D8 Pump systems
Part J6 Air-conditioning and ventilation · NCC 2019: J5.7
(1) General — Pumps and pipework that form part of an air-conditioning system must either—
separately comply with (2), (3), (4), (5), (6) and (7); or
achieve a pump motor power per unit of flowrate lower than the pump motor power per unit of flowrate achieved when applying (2), (3), (4), (5), (6) and (7) together.
(2) Where the pump motor power input at the duty point is greater than 750 W, a pump must be capable of—
variable speed operation; and
where serving a distributive system—
variable volume operation; and
variable pressure operation to the extent permitted by—
static head requirements; and
the requirements of downstream equipment.
(3) A distributive system must not have—
uncontrolled bypasses; or
three port valves.
(4) The requirements of (3)(b) do not apply to a distributive system with a single chiller, including a chiller used for space heating, that serves—
air-conditioning systems with a total co-incident design load of less than 200 kW; or
only one heating coil or one cooling coil.
(5) Circulator pumps — A glandless impeller pump, with a rated hydraulic power output of less than 2.5 kW and that is used in closed loop systems must have an energy efficiency index (EEI) not more than 0.27 calculated in accordance with European Union Commission Regulation No. 622/2012.
(6) Other pumps — Pumps that are in accordance with Articles 1 and 2 of European Union Commission Regulation No. 547/2012 must have a minimum efficiency index (MEI) of 0.4 or more when calculated in accordance with European Union Commission Regulation No. 547/2012.
(7) Pipework — Straight segments of pipework along the index run, forming part of an air-conditioning system—
in pipework systems that do not have branches and have the same flow rate throughout the entire pipe network, must achieve an average pressure drop of not more than—
for constant flow systems, the values nominated in Table J6D8a; or
for variable flow systems, the values nominated in Table J6D8b; or
in any other pipework system, must achieve an average pressure drop of not more than—
for constant flow systems, the values nominated in Table J6D8c; or
for variable flow systems, the values nominated in Table J6D8d.
(8) The requirements of (7) do not apply—
to valves and fittings; or
where the smallest pipe size compliant with (7) results in a velocity of 0.7 m/s or less at design flow.
Table J6D8a Maximum pipework pressure drop – Non-distributive constant flow systems
Nominal pipe diameter (mm)
Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)
Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20
400
400
25
400
400
32
400
400
40
400
400
50
400
350
65
400
350
80
400
350
100
400
200
125
400
200
150 or more
400
200
Table J6D8b Maximum pipework pressure drop – Non-distributive variable flow systems
Nominal pipe diameter (mm)
Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)
Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20
400
400
25
400
400
32
400
400
40
400
400
50
400
400
65
400
400
80
400
400
100
400
300
125
400
300
150 or more
400
300
Table J6D8c Maximum pipework pressure drop – Distributive constant flow systems
Nominal pipe diameter (mm)
Maximum pressure drop in systems operating 2000 hours/annum or less (Pa/m)
Maximum pressure drop in systems operating between 2000 hours/annum and 5000 hrs/yr (Pa/m)
Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20
400
300
150
25
400
220
100
32
400
220
100
40
400
220
100
50
400
220
100
65
400
400
170
80
400
400
170
100
400
400
170
125
400
400
170
150 or more
400
400
170
Table J6D8d Maximum pipework pressure drop – Distributive variable flow systems
Nominal pipe diameter (mm)
Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)
Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20
400
250
25
400
180
32
400
180
40
400
180
50
400
180
65
400
300
80
400
300
100
400
300
125
400
300
150 or more
400
300
Tables
- Table J6D8a Maximum pipework pressure drop – Non-distributive constant flow systems
- Table J6D8b Maximum pipework pressure drop – Non-distributive variable flow systems
- Table J6D8c Maximum pipework pressure drop – Distributive constant flow systems
- Table J6D8d Maximum pipework pressure drop – Distributive variable flow systems
Changed since NCC 2022. See NCC 2022 Volume One J6D8, or show what changed.
(1) General — Pumps and pipework that form part of an air-conditioning system must either — separately comply with (2), (3) (3), (4), (5), (6) and (4); (7); or achieve a pump motor power per unit of flowrate lower than the pump motor power per unit of flowrate achieved when applying (2), (3) (3), (4), (5), (6) and (4) (7) together. (2) Where the pump motor power input at the duty point is greater than 750 W, a pump must be capable of — variable speed operation; and where serving a distributive system — variable volume operation; and variable pressure operation to the extent permitted by — static head requirements; and the requirements of downstream equipment. (3) A distributive system must not have — uncontrolled bypasses; or three port valves. (4) The requirements of (3)(b) do not apply to a distributive system with a single chiller, including a chiller used for space heating, that serves — air-conditioning systems with a total co-incident design load of less than 200 kW; or only one heating coil or one cooling coil. (5) Circulator pumps — A glandless impeller pump, with a rated … calculated in accordance with European Union Commission Regulation No. 622/2012. (3) (6) Other pumps — Pumps that are in accordance with Articles … calculated in accordance with European Union Commission Regulation No. 547/2012. (4) (7) Pipework — Straight segments of pipework along the index run, … average pressure drop of not more than — for constant speed flow systems, the values nominated in Table J6D8a; or for variable speed flow systems, the values nominated in Table J6D8b; or in any … average pressure drop of not more than — for constant speed flow systems, the values nominated in Table J6D8c; or for variable speed flow systems, the values nominated in Table J6D8d. (5) (8) The requirements of (4) (7) do not apply — to valves and fittings; or where the smallest pipe size compliant with (4) (7) results in a velocity of 0.7 m/s or less at design flow. Table J6D8a Maximum pipework pressure drop – Non-distributive constant speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 200 Table J6D8b Maximum pipework pressure drop – Non-distributive variable speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 300 Table J6D8c Maximum pipework pressure drop – Distributive constant speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 170 Table J6D8d Maximum pipework pressure drop – Distributive variable speed flow systems Nominal pipe diameter (mm) Maximum pressure drop in systems … 400 300 125 400 300 150 or more 400 300