Nominal pipe diameter (mm)Maximum pressure drop in systems operating 5000 hours/annum or less (Pa/m)Maximum pressure drop in systems operating more than 5000 hours/annum (Pa/m)
Not more than 20400400
25400400
32400400
40400400
50400400
65400400
80400400
100400300
125400300
150 or more400300

Table for J6D8 Pump systems