Table J7D3b Illumination power density adjustment factor for a control device
Part J7 Artificial lighting and power
| Item Notes 1 and 2 | Description | illumination power density adjustment factor |
|---|---|---|
| Demand-operated controls | In a toilet or change room, other than a public toilet, in a Class 6 building | 0.4 |
| Demand-operated controls | Where a group of light fittings serving less than 100 m2 is controlled by one or more detectors | 0.6 |
| Demand-operated controls | Where a group of light fittings serving 100 m2 or more is controlled by one or more detectors | 0.7 |
| Programmable dimming system Note 3 | Where not less than 75% of the area of a space is controlled by programmable dimmers | 0.85 |
| Fixed dimming Notes 3 and 4 | All fittings with fixed dimming | Whichever is greater of (a) 0.5; or (b) 0.2+0.8L where L = the illuminance turndown for the fixed dimming. |
| Lumen depreciation dimming Note 3 | All fittings with lumen depreciation dimming | 0.85 |
| Two stage sensor - equipped lights with minimum power of 30 % of peak power or less | Fire stairs and other spaces not used for regular transit | 0.4 |
| Two stage sensor - equipped lights with minimum power of 30% of peak power or less | Transitory spaces in regular use or in a carpark | 0.7 |
| Daylight sensor and dynamic lighting control device - dimmed or stepped switching of lights adjacent windows Notes 3 and 5 | In a Class 5, 6, 7, 8 or 9b building or a Class 9a building, other than a ward area, where the lights are adjacent windows, other than roof lights, for a distance from the window equal to the depth of the floor to window head height | 0.5 Note 3 |
| Daylight sensor and dynamic lighting control device - dimmed or stepped switching of lights adjacent windows Notes 3 and 5 | Serving a Class 3 or 9c building, or a Class 9a ward area, where the lights are adjacent windows, other than roof lights, for a distance from the window equal to the depth of the floor to window head height | 0.75 Note 3 |
| Daylight sensor and dynamic lighting control device - dimmed or stepped switching of lights adjacent windows Notes 3 and 5 | In a Class 5, 6, 7, 8 or 9b building or a Class 9a building, other than a ward area, where the lights are adjacent roof lights | 0.6 Note 3 |
| Daylight sensor and dynamic lighting control device - dimmed or stepped switching of lights adjacent windows Notes 3 and 5 | In a Class 3 or 9c building, or a Class 9a ward area, where the lights are adjacent roof lights | 0.8 Note 3 |
Table Notes
A maximum of two illumination power density adjustment factors for a control device can be applied to an area.
Where more than one illumination power density adjustment factor (other than for room aspect) applies to an area, they are to be combined using the following formula: , where—
is the lowest applicable illumination power density adjustment factor; and
is the second lowest applicable illumination power density adjustment factor.
The adjustment factor does not apply to tungsten, halogen or other incandescent sources.
Includes luminaires with a pre-programmed function which provides dimming from ON to OFF (one-stage dimming).
For lighting controlled by daylight sensors, the illumination power density adjustment factor is only applied between 8:00 am and 7:00 pm.
Table for J7D3 Artificial lighting
Changed since NCC 2022. See NCC 2022 Volume One Table J7D3b, or show what changed.
Item Notes 1 and 2 | Description | illumination power density adjustment factor Motion detector Demand-operated controls | In a toilet or change room, other than a public toilet, in a Class 6 building | 0.4 Motion detector Demand-operated controls | Where a group of light fittings serving less than 100 m2 is controlled by one or more detectors | 0.6 Motion detector Demand-operated controls | Where a group of light fittings serving 100 m2 … area, they are to be combined using the following formula: A x (B + [(1 - B)/2]), , where — A is the lowest applicable illumination power density adjustment factor; and B is the second lowest applicable illumination power density adjustment factor. … function which provides dimming from ON to OFF (one-stage dimming). The For lighting controlled by daylight sensors, the illumination power density adjustment factor is only applied to lights controlled by daylight sensors between 8:00 am and 7:00 pm.
Removed words are struck through; added words are highlighted. Comparison of the text only.