NCC 2025 Volume One
Part J7 Artificial lighting and power
14 clauses · Open on NCC Online ↗
- J7D1 Deemed-to-Satisfy Provisions NSWWhere a Deemed-to-Satisfy Solution is proposed, Performance Requirements J1P1 to J1P4 are satisfied by complying with— J2D2; and J3D2 to J3D15; and…
- J7D2 Application of PartJ7D3, J7D4 and J7D6(1)(b) do not apply to a Class 8 electricity network substation.
- Table J7D3a Maximum illumination power densitySpace | Maximum illumination power density (W/m2) Auditorium, church and public hall | 8 Board room and conference room | 5 Carpark - general | 2…
- Table J7D3b Illumination power density adjustment factor for a control deviceItem Notes 1 and 2 | Description | illumination power density adjustment factor Demand-operated controls | In a toilet or change room, other than a…
- Table J7D3c Illumination power density adjustment factor for light colourLight source | Description | Illumination power density adjustment factor CRI ≥ 90 | Where lighting with good colour rendering is used | 0.9 CCT ≤…
- J7D3 Artificial lighting NSWIn a Class 4 part of a building— the lamp power density or illumination power density of artificial lighting must not exceed the allowance of— 5…
- J7D4 Interior artificial lighting and power control NSWIn a Class 4 part of a building, all artificial lighting of a room or space must be individually operated in accordance with Specification 40 by– a…
- J7D5 Interior decorative and display lightingInterior decorative and display lighting, such as for a foyer mural or art display, must be controlled— separately from other artificial lighting;…
- J7D6 Exterior artificial lightingExterior artificial lighting attached to or directed at the facade of a building, must— be controlled by— a daylight sensor; or a time switch that…
- J7D7 Boiling water and chilled water storage unitsPower supply to a boiling water or chilled water storage unit must be controlled by a time switch in accordance with Specification 40.
- Table J7D8a Lift idle and standby energy performance levelRated load | Idle and standby energy performance level in accordance with ISO 25745-2 Note ≤ 800 kg | 2 > 800 kg to ≤ 2000 kg | 3 > 2000 kg to ≤…
- Table J7D8b Lift energy efficiency classUsage category in accordance with ISO 25745-2 | Energy efficiency class in accordance with ISO 25745-2 1-4 | C ≥ 5 | D
- J7D8 LiftsLifts must— be configured to ensure artificial lighting and ventilation in the car are turned off when it is unused for 15 minutes; and achieve the…
- J7D9 Escalators and moving walkwaysEscalators and moving walkways must have the ability to slow to between 0.2 m/s and 0.05 m/s when unused for more than 15 minutes.