Table J7D3a Maximum illumination power density
Part J7 Artificial lighting and power
| Space | Maximum illumination power density (W/m2) |
|---|---|
| Auditorium, church and public hall | 8 |
| Board room and conference room | 5 |
| Carpark - general | 2 |
| Carpark - entry zone (first 15 m of travel) during the daytime | 11.5 |
| Carpark - entry zone (next 4 m of travel) during the day | 2.5 |
| Carpark - entry zone (first 20 m of travel) during night time | 2.5 |
| Common rooms, spaces and corridors in a Class 2 building | 4.5 |
| Control room, switch room and the like - intermittent monitoring | 3 |
| Control room, switch room and the like - constant monitoring | 4.5 |
| Corridors | 5 |
| Courtroom | 4.5 |
| Dormitory of a Class 3 building used for sleeping only | 3 |
| Dormitory of a Class 3 building used for sleeping and study | 4 |
| Entry lobby from outside the building | 9 |
| Health-care - infants' and children's wards and emergency department | 4 |
| Health-care - examination room | 4.5 |
| Health-care - examination room in intensive care and high dependency ward | 6 |
| Health-care - all other patient care areas including wards and corridors | 2.5 |
| Kitchen and food preparation area | 4 |
| Laboratory - artificially lit to an ambient level of 400 lx or more | 6 |
| Library - stack and shelving area | 2.5 |
| Library - reading room and general areas | 4.5 |
| Lounge area for communal use in a Class 3 or 9c building | 4.5 |
| Museum and gallery - circulation, cleaning and service lighting | 2.5 |
| Office - artificially lit to an ambient level of 200 lx or more | 4.5 |
| Office - artificially lit to an ambient level of less than 200 lx | 2.5 |
| Plant room where an average of 160 lx vertical illuminance is required on a vertical panel such as in switch rooms | 4 |
| Plant rooms with a horizontal illuminance target of 80 lx | 2 |
| Restaurant, café, bar, hotel lounge and a space for the serving and consumption of food or drinks | 14 |
| Retail space including a museum and gallery whose purpose is the sale of objects | 14 |
| School - general purpose learning areas and tutorial rooms | 4.5 |
| Sole-occupancy unit of a Class 3 or 9c building | 5 |
| Storage | 1.5 |
| Service area, cleaner's room and the like | 1.5 |
| Toilet, locker room, staff room, rest room and the like | 3 |
| Wholesale storage area with a vertical illuminance target of 160 lx | 4 |
| Stairways, including fire-isolated stairways | 2 |
| Lift cars | 5.5 |
Table Notes
In areas not listed above, the maximum illumination power density is—
for an illuminance not more than 80 lx, 2 W/m2; and
for an illuminance more than 80 lx and not more than 160 lx, 2.5 W/m2; and
for an illuminance more than 160 lx and not more than 240 lx, 3 W/m2; and
for an illuminance more than 240 lx and not more than 320 lx, 4.5 W/m2; and
for an illuminance more than 320 lx and not more than 400 lx, 6 W/m2; and
for an illuminance more than 400 lx and not more than 600 lx, 10 W/m2; and
for an illuminance more than 600 lx and not more than 800 lx, 11.5 W/m2.
For enclosed spaces with a Room Aspect Ratio of less than 1.5, the maximum illumination power density may be increased by dividing it by an adjustment factor for room aspect which is 0.5 + (Room Aspect Ratio/3).
The Room Aspect Ratio of the enclosed space is determined by the formula: A/(H x C), where—
A is the area of the enclosed space; and
H is the height of the space measured from the floor to the highest part of the ceiling; and
C is the perimeter of the enclosed space at floor level.
In addition to 2, the maximum illumination power density may be increased by dividing it by the illumination power density adjustment factor in Table J7D3b and Table J7D3c.
Circulation spaces are included in the allowances listed in this table.
Table for J7D3 Artificial lighting
Changed since NCC 2022. See NCC 2022 Volume One Table J7D3a, or show what changed.
Space | Maximum illumination power density (W/m2) Auditorium, church and … 4 Stairways, including fire-isolated stairways | 2 Lift cars | 3 5.5 Table Notes In areas not listed above, the maximum illumination … illumination power density adjustment factor in Table J7D3b and Table J7D3c and where the control device is not installed to comply with J6D4. J7D3c. Circulation spaces are included in the allowances listed in the Table. this table.