Table · NCC 2025 Volume One

Table J7D3a Maximum illumination power density

Part J7 Artificial lighting and power

Open Table J7D3a on NCC Online ↗
SpaceMaximum illumination power density (W/m2)
Auditorium, church and public hall8
Board room and conference room5
Carpark - general2
Carpark - entry zone (first 15 m of travel) during the daytime11.5
Carpark - entry zone (next 4 m of travel) during the day2.5
Carpark - entry zone (first 20 m of travel) during night time2.5
Common rooms, spaces and corridors in a Class 2 building4.5
Control room, switch room and the like - intermittent monitoring3
Control room, switch room and the like - constant monitoring4.5
Corridors5
Courtroom4.5
Dormitory of a Class 3 building used for sleeping only3
Dormitory of a Class 3 building used for sleeping and study4
Entry lobby from outside the building9
Health-care - infants' and children's wards and emergency department4
Health-care - examination room4.5
Health-care - examination room in intensive care and high dependency ward6
Health-care - all other patient care areas including wards and corridors2.5
Kitchen and food preparation area4
Laboratory - artificially lit to an ambient level of 400 lx or more6
Library - stack and shelving area2.5
Library - reading room and general areas4.5
Lounge area for communal use in a Class 3 or 9c building4.5
Museum and gallery - circulation, cleaning and service lighting2.5
Office - artificially lit to an ambient level of 200 lx or more4.5
Office - artificially lit to an ambient level of less than 200 lx2.5
Plant room where an average of 160 lx vertical illuminance is required on a vertical panel such as in switch rooms4
Plant rooms with a horizontal illuminance target of 80 lx2
Restaurant, café, bar, hotel lounge and a space for the serving and consumption of food or drinks14
Retail space including a museum and gallery whose purpose is the sale of objects14
School - general purpose learning areas and tutorial rooms4.5
Sole-occupancy unit of a Class 3 or 9c building5
Storage1.5
Service area, cleaner's room and the like1.5
Toilet, locker room, staff room, rest room and the like3
Wholesale storage area with a vertical illuminance target of 160 lx4
Stairways, including fire-isolated stairways2
Lift cars5.5

Table Notes

In areas not listed above, the maximum illumination power density is—

for an illuminance not more than 80 lx, 2 W/m2; and

for an illuminance more than 80 lx and not more than 160 lx, 2.5 W/m2; and

for an illuminance more than 160 lx and not more than 240 lx, 3 W/m2; and

for an illuminance more than 240 lx and not more than 320 lx, 4.5 W/m2; and

for an illuminance more than 320 lx and not more than 400 lx, 6 W/m2; and

for an illuminance more than 400 lx and not more than 600 lx, 10 W/m2; and

for an illuminance more than 600 lx and not more than 800 lx, 11.5 W/m2.

For enclosed spaces with a Room Aspect Ratio of less than 1.5, the maximum illumination power density may be increased by dividing it by an adjustment factor for room aspect which is 0.5 + (Room Aspect Ratio/3).

The Room Aspect Ratio of the enclosed space is determined by the formula: A/(H x C), where—

A is the area of the enclosed space; and

H is the height of the space measured from the floor to the highest part of the ceiling; and

C is the perimeter of the enclosed space at floor level.

In addition to 2, the maximum illumination power density may be increased by dividing it by the illumination power density adjustment factor in Table J7D3b and Table J7D3c.

Circulation spaces are included in the allowances listed in this table.

Table for J7D3 Artificial lighting

Changed since NCC 2022. See NCC 2022 Volume One Table J7D3a, or show what changed.

Space | Maximum illumination power density (W/m2) Auditorium, church and … 4 Stairways, including fire-isolated stairways | 2 Lift cars | 3 5.5 Table Notes In areas not listed above, the maximum illumination … illumination power density adjustment factor in Table J7D3b and Table J7D3c and where the control device is not installed to comply with J6D4. J7D3c. Circulation spaces are included in the allowances listed in the Table. this table.