Table S5C24d Type C construction: FRL of internal walls
Specification 5 Fire-resisting construction
| Location | FRL (in minutes): Structural adequacy / Integrity / Insulation | |||
|---|---|---|---|---|
| Class 2, 3 or 4 part | Class 5, 7a or 9 | Class 6 | Class 7b or 8 | |
| Bounding public corridors, public lobbies and the like | 60/60/60 | –/–/– | –/–/– | –/–/– |
| Between or bounding sole-occupancy units | 60/60/60 | –/–/– | –/–/– | –/–/– |
| Bounding a stair if required to be rated | 60/60/60 | 60/60/60 | 60/60/60 | 60/60/60 |
Table for S5C24 Type C fire-resisting construction — fire-resistance of building elements
Same wording in NCC 2022 Volume One. See NCC 2022 Volume One Table S5C24d.