Specification clause · NCC 2025 Volume One

S5C24 Type C fire-resisting construction — fire-resistance of building elements

Specification 5 Fire-resisting construction · NCC 2019: Spec C1.1: 5.1 and Table 5

Open S5C24 on NCC Online ↗

(1) In a building required to be of Type C construction—

a building element listed in Tables S5C24a, S5C24b, S5C24c, S5C24d and S5C24e and any beam or column incorporated in it, must have an FRL not less than that listed in those Tables for the particular Class of building concerned; and

an external wall that is required by Table S5C24a to have an FRL need only be tested from the outside to satisfy the requirement; and

a fire wall or an internal wall bounding a sole-occupancy unit or separating adjoining units must comply with Specification 6 if it is of lightweight construction and is required to have an FRL; and

in a Class 2 or 3 building, an internal wall which is required by S5C24c or S5C24d to have an FRL must extend—

to the underside of the floor next above if that floor has an FRL of at least 30/30/30 or a fire-protective covering on the underside of the floor; or

to the underside of a ceiling having a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or

to the underside of the roof covering if it is non-combustible, and except for roof battens with dimensions of 75 mm x 50 mm or less or sarking-type material, must not be crossed by timber or other combustible building elements; or

450 mm above the roof covering if it is combustible; and

in a Class 2 or 3 building, except where within the one sole-occupancy unit, or a Class 9a health-care building, or a Class 9b building, a floor separating storeys, or above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—

have an FRL of at least 30/30/30; or

have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal; and

in a Class 9c building a floor above a space for the accommodation of motor vehicles or used for storage or any other ancillary purpose, and any column supporting the floor, must—

have an FRL of at least 30/30/30; or

have a fire-protective covering on the underside of the floor including beams incorporated in it and around the column, if the floor or column is combustible or of metal.

(2) For the purposes of Table S5C24a and Table S5C24b, external wall includes any column and other building element incorporated within it or other external building element.

Table S5C24a Type C construction: FRL of parts of external walls

Distance from a fire-source feature

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Less than 1.5 m

90/90/90

90/90/90

90/90/90

90/90/90

1.5 to less than 3 m

–/–/–

60/60/60

60/60/60

60/60/60

3 m or more

–/–/–

–/–/–

–/–/–

–/–/–

Table S5C24b Type C construction: FRL of external columns not incorporated into an external wall

Distance from a fire-source feature

FRL (in minutes): structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Less than 1.5 m

90/–/–

90/–/–

90/–/–

90/–/–

1.5 to less than 3 m

–/–/–

60/–/–

60/–/–

60/–/–

3 m or more

–/–/–

–/–/–

–/–/–

–/–/–

Table S5C24c Type C construction: FRL of common walls and fire walls

Wall type

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Load bearing or non-load bearing

90/90/90

90/90/90

90/90/90

90/90/90

Table S5C24d Type C construction: FRL of internal walls

Location

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Bounding public corridors, public lobbies and the like

60/60/60

–/–/–

–/–/–

–/–/–

Between or bounding sole-occupancy units

60/60/60

–/–/–

–/–/–

–/–/–

Bounding a stair if required to be rated

60/60/60

60/60/60

60/60/60

60/60/60

Table S5C24e Type C construction: FRL of roof

Location

FRL (in minutes): Structural adequacy / Integrity / Insulation

Class 2, 3 or 4 part

Class 5, 7a or 9

Class 6

Class 7b or 8

Roofs

–/–/–

–/–/–

–/–/–

–/–/–

Tables

Changed since NCC 2022. See NCC 2022 Volume One S5C24, or show what changed.

(1) In a building required to be of Type C … or 3 building, an internal wall which is required by Table 5C24c S5C24c or S5C24d to have an FRL must extend — to … 5, 7a or 9 Class 6 Class 7b or 8 Loadbearing Load bearing or non-loadbearing non-load bearing 90/90/90 90/90/90 90/90/90 90/90/90 Table S5C24d Type C construction: FRL … 6 Class 7b or 8 Roofs –/–/– –/–/– –/–/– –/–/–

Removed words are struck through; added words are highlighted. Comparison of the text only.