VIC D2D9 Width of doorways in exits or paths of travel to exits
VIC Part D2 Provision for escape · varies D2D9 Width of doorways in exits or paths of travel to exits
Delete clause D2D9 and insert VIC D2D9 as follows:
(1) In a required exit or path of travel to an exit, the unobstructed width of a doorway must be not less than—
in patient care areas through which patients would normally be transported in beds—
if the doorway provides access to, or from, a corridor of width—
less than 2.2 m — 1200 mm; or
2.2 m or greater — 1070 mm; and
where the doorway referred to in (i) is fitted with two leaves and one leaf is secured in the closed position in accordance with D3D26(3)(e), the other leaf must permit an unobstructed opening not less than 800 mm wide; or
in patient care areas in a horizontal exit — 1250 mm; or
the unobstructed width of each exit provided to comply with D2D8(1), (2), (3) or (4), minus 250 mm; or
in any other case except where it opens to a sanitary compartment or bathroom — 750 mm wide.
(2) Notwithstanding (1), in Class 3 and Class 9a residential aged care buildings, the unobstructed width of all bedroom entrance doorways must be not less than 900 mm.
Changed since NCC 2022. See NCC 2022 Volume One VIC D2D9, or show what changed.
Delete clause D2D9 and insert VIC D2D9 as follows: (1) In a required exit or path of travel to an … to a sanitary compartment or bathroom — 750 mm wide. (2) Notwithstanding (1), in Class 3 and Class 9a residential aged care buildings, the unobstructed width of all bedroom entrance doorways must be not less than 900 mm.