Victoria variation · NCC 2025 Volume One

VIC E1D6 Where sprinklers are required: Class 2 and 3 buildings other than residential care buildings

VIC Part E1 Fire fighting equipment · varies E1D6 Where sprinklers are required: Class 2 and 3 buildings other than residential care buildings

Open on NCC Online ↗

Delete clause E1D6 and insert VIC E1D6 as follows:

(1) Sprinklers are required throughout—

A shared accommodation building; and

In a Class 2 or 3 building, or any multi-classified building containing a Class 2 or 3 part, if any part of the building has—

a rise in storeys of 4 or more; and

an effective height of not more than 25 m.

(2) The requirements of (1) do not apply to—

a residential care building; and

a Class 8 electricity network substation with a floor area not more than 200 m2 located within a multi-classified building.

New in NCC 2025. No VIC E1D6 in NCC 2022 Volume One; it may have moved or been renumbered.

The national clause