E1D6 Where sprinklers are required: Class 2 and 3 buildings other than residential care buildings
Part E1 Fire fighting equipment · NCC 2019: Table E1.5
(1) In a Class 2 or 3 building, or any multi-classified building containing a Class 2 or 3 part, sprinklers are required throughout the whole building if any part of the building has—
a rise in storeys of 4 or more; and
an effective height of not more than 25 m.
(2) The requirements of (1) do not apply to—
a residential care building; and
a Class 8 electricity network substation with a floor area not more than 200 m2 located within a multi-classified building.