Housing Provisions clause · ABCB Housing Provisions 2022

10.2.24 Flashings/junctions

Part 10.2 Wet area waterproofing

Open 10.2.24 on NCC Online ↗

Flashings must be installed in accordance with 10.2.2 to 10.2.5 and the following:

Perimeter flashing to wall/floor junctions must have a—

vertical leg that extends a minimum of 25 mm above the finished floor level, except across doorways; and

horizontal leg that has a minimum width of not less than 50 mm.

Where a water resistant substrate is used in conjunction with a water resistant surface material, a waterproof sealant must be installed at the substrate junction at the wall/floor junction.

Perimeter flashings at a floor level opening must comply with the following:

Where the whole wet area floor is waterproof, at floor level openings, a waterstop must be installed that has a vertical leg finishing flush with the top of the finished floor level with the floor membrane being terminated to create a waterproof seal to the waterstop and to the perimeter flashing (see Figure 10.2.24).

In any other case, at a floor level opening a waterstop must be installed that has a vertical leg finishing flush with the top of the finished floor level and waterproofed to the perimeter flashing.

A vertical flashing, either external to the wet area or internal, must extend a minimum of 1800 mm above the finished floor level.

Figure 10.2.24 Typical bathroom door details for whole bathroom waterproofing

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 10.2.24.