11.3.4 Construction of barriers to prevent falls
Part 11.3 Barriers and handrails · NCC 2019: 3.9.2.3
(1) A barrier required by 11.3.3 must comply with (2) to (11).
(2) The height of a barrier must be in accordance with the following:
The height must not be less than 865 mm above the nosings of the stair treads, the floor of a ramp or the like (see Figure 11.3.4a).
The height must not be less than—
1 m above the floor of any landing, corridor, hallway, balcony, deck, verandah, access path, mezzanine, access bridge, roof top space or the like to which general access is provided (see Figure 11.3.3b and Figure 11.3.4a); or
865 mm above the floor of a landing to a stairway or ramp where the barrier is provided along the inside edge of the landing and does not exceed a length of 500 mm.
(3) A transition zone may be incorporated where the barrier height changes from 865 mm on the stairway flight or ramp to 1 m at the landing (see Figure 11.3.4b).
(4) Openings in barriers (including decorative balustrades) must be constructed so that they do not permit a 125 mm sphere to pass through it and for stairways, the opening is measured above the nosing line of the stair treads (see Figure 11.3.4a).
(5) Where a required barrier is fixed to the vertical face forming an edge of a landing, balcony, deck, stairway or the like, the opening formed between the barrier and the face must not exceed 40 mm.
(6) For the purposes of (5), the opening is measured horizontally from the edge of the trafficable surface to the nearest internal face of the barrier.
(7) A barrier to a stairway serving a non-habitable room, such as an attic, storeroom or the like that is not used on a regular or daily basis, need not comply with (4) if—
openings are constructed so that they do not permit a 300 mm sphere to pass through; or
where rails are used, the barrier consists of a top rail and an intermediate rail, with the openings between rails not more than 460 mm.
(8) Restriction on horizontal elements:
Where it is possible to fall more than 4 m, any horizontal elements within the barrier between 150 mm and 760 mm above the floor must not facilitate climbing.
For the purpose of (a), the 4 m is measured from the floor level of the trafficable surface to the surface beneath.
(9) A barrier constructed of wire is deemed to meet the requirements of (4) if it is constructed in accordance with 11.3.6.
(10) A glass barrier or window serving as a barrier must comply with H1D8 and the relevant provisions of this Part.
(11) A barrier, except a window serving as a barrier, must be designed to take loading forces in accordance with AS/NZS 1170.1.
Figure 11.3.4a Barrier construction
Figure 11.3.4b Measuring heights for barriers and handrails and where transition zones are allowed