11.3.3 Barriers to prevent falls
Part 11.3 Barriers and handrails · NCC 2019: 3.9.2.2
(1) A continuous barrier must be provided along the side of a trafficable surface, such as—
a stairway, ramp or the like; and
a floor, corridor, hallway, balcony, deck, verandah, mezzanine, access bridge or the like; and
a roof top space or the like to which general access is provided; and
any delineated path of access to a building,
where it is possible to fall 1 m or more measured from the level of the trafficable surface to the surface beneath (see Figure 11.3.3a).
(2) The requirements of (1) do not apply to—
a retaining wall unless the retaining wall forms part of, or is directly associated with, a delineated path of access to a building from the road, or a delineated path of access between buildings (see Figure 11.3.3b); or
a barrier provided to an openable window covered by 11.3.7 and 11.3.8.
Figure 11.3.3a Barriers — when required
Figure 11.3.3b Barriers — when required for retaining walls
Changed in NCC 2025. See ABCB Housing Provisions 2025 11.3.3, or show what changed.
(1) A continuous barrier must be provided along the side … barrier provided to an openable window covered by 11.3.7 and 11.3.8. 11.3.8; or a barrier complying with AS 1657 serving a fixed platform, walkway, stairway or ladder provided in accordance with 11.2.7(a). Figure 11.3.3a Barriers — when required Figure 11.3.3b Barriers — when required for retaining walls