13.7.3 Central heating water piping
Part 13.7 Services · NCC 2019: 3.12.5.2
(1) Central heating water piping that is not within a conditioned space must be thermally insulated to achieve the minimum material R-Values as set out in (2) to (6).
(2) Internal piping including—
flow and return piping that is—
within an unventilated wall space; or
within an internal floor between storeys; or
between ceiling insulation and a ceiling; and
heated water piping encased within a concrete floor slab (except that which is part of a floor heating system),
must, in all climate zones, have a minimum material R-Value of 0.4.
(3) Piping located within a ventilated wall space, an enclosed building subfloor or a roof space, including—
flow and return piping; and
cold water supply piping within 500 mm of the connection to the central water heating system; and
relief valve piping within 500 mm of the connection to the central water heating system,
must have a minimum material R-Value in accordance with (5).
(4) Piping located outside the building or in an unenclosed building subfloor or roof space, including—
flow and return piping; and
cold water supply piping within 500 mm of the connection to the central water heating system; and
relief valve piping within 500 mm of the connection to the central water heating system,
must have a minimum material R-Value in accordance with (6).
(5) Piping referred to in (3) must have a minimum material R-Value of—
in climate zones 1, 2, 3 and 5 — 0.6; and
in climate zones 4, 6 and 7 — 0.9; and
in climate zone 8 — 1.3.
(6) Piping referred to in (4) must have a minimum material R-Value of—
in climate zones 1, 2, 3 and 5 — 0.6; and
in climate zones 4, 6 and 7 — 1.3; and
in climate zone 8 — 1.3.