NT 13.7.3 Central heating water piping
NT Part 13.7 Services · varies 13.7.3 Central heating water piping
(1) Central heating water piping that is not within a conditioned space must be thermally insulated to achieve the minimum Total R-Value of 0.6.
(2) Internal piping including—
flow and return piping that is—
within an unventilated wall space; or
within an internal floor between storeys; or
between ceiling insulation and a ceiling; and
heated water piping encased in a concrete floor slab (except that which is part of a floor heating system), must in all climate zones, have a minimum material R-Value of 0.4.
(3) All piping located outside a building, or within a ventilated wall space, subfloor or roof space must have a minimum material R-Value of 0.6.