7.5.3 Wall cladding boards

Part 7.5 Timber and composite wall cladding · NCC 2019: 3.5.4.3

Open 7.5.3 on NCC Online ↗

Wall cladding boards must—

for 7.5 mm (minimum) thick fibre-cement — comply with AS/NZS 2908.2 or ISO 8336; and

for 9.5 mm (minimum) thick hardboard — comply with AS/NZS 1859.4 for exterior grade; and

be fixed in accordance with Table 7.5.3a and Table 7.5.3b with—

one fixing provided at each stud or equivalent framing member for wall cladding boards not more than 130 mm wide; and

two fixings provided at each stud or equivalent framing member for wall cladding boards greater than 130 mm wide; and

fixings located along the studs at not more than 100 mm centres; and

fixings located so that they do not penetrate the tip or thinner edge of the board beneath; and

have a lap not less than—

for 7.5 mm (minimum) thick fibre-cement — 25mm; or

for 9.5 mm (minimum) thick hardboard — 20 mm.

Table 7.5.3a Fixing requirements—Minimum 7.5 mm thick fibre-cement wall cladding boards

Wind class

Maximum stud spacing (mm)

Minimum nominal stud fixings

N1 - N3

600

Timber: 2.8 GC

Steel: (8-18) S

Table Notes

GC = galvanised fibre-cement nail.

S = self embedding or wafer head screw.

Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.

Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.

Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.

Table 7.5.3b Fixing requirements—Minimum 9.5 mm thick hardboard wall cladding boards

Wind class

Maximum stud spacing (mm)

Minimum nominal stud fixings

N1 - N3

600

Timber: 2.8 GC

Steel: (8-18) S

Table Notes

GC = galvanised fibre-cement nail.

S = self embedding or wafer head screw.

Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.

Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.

Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.

Tables

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 7.5.3.