7.5.3 Wall cladding boards
Part 7.5 Timber and composite wall cladding · NCC 2019: 3.5.4.3
Wall cladding boards must—
for 7.5 mm (minimum) thick fibre-cement — comply with AS/NZS 2908.2 or ISO 8336; and
for 9.5 mm (minimum) thick hardboard — comply with AS/NZS 1859.4 for exterior grade; and
be fixed in accordance with Table 7.5.3a and Table 7.5.3b with—
one fixing provided at each stud or equivalent framing member for wall cladding boards not more than 130 mm wide; and
two fixings provided at each stud or equivalent framing member for wall cladding boards greater than 130 mm wide; and
fixings located along the studs at not more than 100 mm centres; and
fixings located so that they do not penetrate the tip or thinner edge of the board beneath; and
have a lap not less than—
for 7.5 mm (minimum) thick fibre-cement — 25mm; or
for 9.5 mm (minimum) thick hardboard — 20 mm.
Table 7.5.3a Fixing requirements—Minimum 7.5 mm thick fibre-cement wall cladding boards
Wind class
Maximum stud spacing (mm)
Minimum nominal stud fixings
N1 - N3
600
Timber: 2.8 GC
Steel: (8-18) S
Table Notes
GC = galvanised fibre-cement nail.
S = self embedding or wafer head screw.
Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.
Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Table 7.5.3b Fixing requirements—Minimum 9.5 mm thick hardboard wall cladding boards
Wind class
Maximum stud spacing (mm)
Minimum nominal stud fixings
N1 - N3
600
Timber: 2.8 GC
Steel: (8-18) S
Table Notes
GC = galvanised fibre-cement nail.
S = self embedding or wafer head screw.
Fasteners must penetrate not less than 30 mm into timber frames and not less than two full screw threads through steel frames.
Steel framing members must have a base metal thickness (BMT) not less than that required for a roof batten in NASH standard.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Tables
- Table 7.5.3a Fixing requirements—Minimum 7.5 mm thick fibre-cement wall cladding boards
- Table 7.5.3b Fixing requirements—Minimum 9.5 mm thick hardboard wall cladding boards