Table · ABCB Housing Provisions 2022

Table 7.5.4a Stud and fixing spacings for 6 mm fibre-cement sheet wall cladding

Part 7.5 Timber and composite wall cladding

Open Table 7.5.4a on NCC Online ↗
Wind classMaximum stud spacing (mm)Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1Maximum nail spacing elsewhere (mm) Note 1
N1≤ 1.2 m of external building corners: 600 Elsewhere: 600Body: 300, Edges: 200Body: 300, Edges: 200
N2≤ 1.2 m of external building corners: 600 Elsewhere: 600Body: 200, Edges: 200Body: 300, Edges: 200
N3≤ 1.2 m of external building corners: 450 Elsewhere: 600Body: 200, Edges: 200Body: 200, Edges: 200

Table Notes

Maximum nail spacing using 2.8 mm fibre-cement nails.

Fixings must be located not less than 50 mm from the edge of all corners.

Fasteners must penetrate not less than 30 mm into a timber frame.

Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.

Table for 7.5.4 Sheet wall cladding

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 7.5.4a.