7.5.4 Sheet wall cladding
Part 7.5 Timber and composite wall cladding · NCC 2019: 3.5.4.4
(1) Fibre-cement sheet wall cladding must—
comply with AS/NZS 2908.2 or ISO 8336; and
be fixed in accordance with Table 7.5.4a.
(2) Hardboard sheet wall cladding must—
comply with AS/NZS 1859.4 for exterior grade; and
be fixed in accordance with Table 7.5.4b.
(3) Structural plywood wall cladding must—
comply with AS/NZS 2269.0; and
be fixed in accordance with Table 7.5.4c.
Table 7.5.4a Stud and fixing spacings for 6 mm fibre-cement sheet wall cladding
Wind class
Maximum stud spacing (mm)
Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1
Maximum nail spacing elsewhere (mm) Note 1
N1
≤ 1.2 m of external building corners: 600 Elsewhere: 600
Body: 300, Edges: 200
Body: 300, Edges: 200
N2
≤ 1.2 m of external building corners: 600 Elsewhere: 600
Body: 200, Edges: 200
Body: 300, Edges: 200
N3
≤ 1.2 m of external building corners: 450 Elsewhere: 600
Body: 200, Edges: 200
Body: 200, Edges: 200
Table Notes
Maximum nail spacing using 2.8 mm fibre-cement nails.
Fixings must be located not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into a timber frame.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Table 7.5.4b Stud and fixing spacings for 9.5 mm thick hardboard sheet wall cladding
Wind class
Maximum stud spacing (mm)
Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1
Maximum nail spacing elsewhere (mm) Note 1
N1
600
Body: 300, Edges: 150
Body: 300, Edges: 150
N2
600
Body: 300, Edges: 150
Body: 300, Edges: 150
N3
600
Body: 300, Edges: 150
Body: 300, Edges: 150
Table Notes
Maximum nail spacing using 2.8 mm galvanised clouts or flat head nails.
Fixings must be positioned a minimum of 12 mm from the edge of the sheet and not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into the timber frame.
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Table 7.5.4c Stud and fixing spacings for plywood wall cladding equal to or greater than 6.5 mm thick
Wind class
Maximum stud spacing (mm)
Maximum nail spacing within 1.2 m of the external corners of the building (mm) Note 1
Maximum nail spacing elsewhere (mm) Note 1
N1
600
Body: 200, Edges: 100
Body: 200, Edges: 150
N2
600
Body: 200, Edges: 100
Body: 200, Edges: 150
N3
600
Body: 150, Edges: 100
Body: 200, Edges: 150
Table Notes
Maximum nail spacing using 2.8 mm or 3.5 mm galvanised clouts or flat head nails.
Fixings must be positioned a minimum of 12 mm from the edge of the sheet and not less than 50 mm from the edge of all corners.
Fasteners must penetrate not less than 30 mm into the timber frame
Wall cladding may be fixed through timber or metal battens attached to the wall frame in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or NASH standard as appropriate (see fixing requirements for roof battens) so long as the minimum penetration into the wall frame is achieved.
Tables
- Table 7.5.4a Stud and fixing spacings for 6 mm fibre-cement sheet wall cladding
- Table 7.5.4b Stud and fixing spacings for 9.5 mm thick hardboard sheet wall cladding
- Table 7.5.4c Stud and fixing spacings for plywood wall cladding equal to or greater than 6.5 mm thick