Table · ABCB Housing Provisions 2022

Table 13.2.3q Flat, skillion or cathedral roof – minimum R-Value for ceiling insulation: climate zone 7

Part 13.2 Building fabric

Open Table 13.2.3q on NCC Online ↗
Reflective insulation under-roofSA ≤ 0.230.23 < SA ≤ 0.320.32 < SA ≤ 0.420.42 < SA ≤ 0.530.53 < SA ≤ 0.640.64 < SA ≤ 0.730.73 < SA ≤ 0.850.85 < SA ≤ 0.96
Yes4.54.54.54.04.04.04.04.0
No5.04.54.54.04.03.53.53.5

Table Notes

SA = solar absorptance.

The R-Value can be achieved by installing insulation under the roof or on top of the ceiling or a combination of both.

The R-Value of reflective insulation is not to be included in the R-Value of any under-roof or ceiling insulation.

R-Values listed are for the labelled, declared R-Value of insulation.

Table for 13.2.3 Roofs and ceilings

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.3q.

Defined terms used