Table 13.2.6i Metal-framed suspended floor — minimum Total R-Value for floor to account for thermal bridging

Part 13.2 Building fabric

Open Table 13.2.6i on NCC Online ↗
Floor insulation from Tables 13.2.6a and 13.2.6d to 13.2.6h as applicableFloor coveringMinimum Total R-Value of floor
0.0Carpet0.36
0.0Other0.22
0.5Carpet0.86
0.5Other0.71
1.0Carpet1.30
1.0Other1.15
1.5Carpet1.65
1.5Other1.50
2.0Carpet1.97
2.0Other1.83
2.5Carpet2.27
2.5Other2.11
3.0Carpet2.52
3.0Other2.37
3.5Carpet2.59
3.5Other2.47
4.0Carpet2.79
4.0Other2.65

Table Notes

The Total R-Value can be adjusted using area weightings where there is a combination of floor coverings. Invert the Total R-Value for each floor type before applying area weightings.

The Total R-Value for the floor plane only includes the floor frame, insulation, flooring and floor coverings. It does not include the internal air film, subfloor airspace, subfloor walls or external air film.

Minimum Total R-Values are in-situ values. They account for compression of insulation.

Direction of heat flow must be determined in accordance with Table 13.2.6k.

Table for 13.2.6 Floors and subfloor walls

Same wording in ABCB Housing Provisions 2025. See ABCB Housing Provisions 2025 Table 13.2.6i.