Table 4.2.13b Stumps supporting single storey tiled floor and tiled roof

Part 4.2 Footings, slabs and associated elements

Open Table 4.2.13b on NCC Online ↗
Floor load area (m2)Dimension (mm)Roof load area (m2)
0612
3Square pad footing size300 x 300400 x 400450 x 450
8Square pad footing size450 x 450500 x 500550 x 500
12Square pad footing size500 x 500550 x 550600 x 600
3Circular pad footing diameter400450600
8Circular pad footing diameter600600650
12Circular pad footing diameter650650700
3Pad footing depth250250250
8Pad footing depth250250250
12Pad footing depth250300300

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.

Minimum bearing pressure is 100 kPa for pad footings.

For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.

Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of length/100 has been accounted for in the stumps.

A roof load area of “0” must be used for stumps not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table for 4.2.13 Stump footing details