Housing Provisions clause · ABCB Housing Provisions 2022

4.2.13 Stump footing details

Part 4.2 Footings, slabs and associated elements · NCC 2019: 3.2.5.6

Open 4.2.13 on NCC Online ↗

(1) Footings for stumps must comply with—

the provisions of Tables 4.2.13a, 4.2.13b or 4.2.13c for Class A and Class S sites; or

the appropriate referenced document listed in—

H1D6(3); or

H1D4.

(2) Concrete stumps must—

be designed in accordance with—

AS 3600; or

Tables 4.2.13d, 4.2.13e or 4.2.13f; and

use a minimum 20 MPa concrete as defined in AS 3600.

(3) Steel stumps must be—

designed in accordance with—

AS 4100; or

Tables 4.2.13d, 4.2.13e or 4.2.13f; and

fully enclosed and sealed with a welded top plate; and

encased in concrete sloping away from the stump and finishing not less than 100 mm above finished ground level; and

corrosion protected in accordance with Part 6.3.

(4) Timber stumps must be designed in accordance with—

AS 1684.2, AS 1684.3, AS 1684.4 or AS 1720.1; or

Tables 4.2.13d, 4.2.13e or 4.2.13f.

(5) Stumps must be braced—

by a full perimeter masonry base; or

for concrete stumps — in accordance with AS 3600; or

for steel stumps — in accordance with AS 4100; or

for timber stumps — in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or AS 1720.1.

(6) Stumps must be embedded into the foundation material not less than 30% of their height above ground level or 450 mm, whichever is the greater.

(7) Pad footings for clad frame, Class A and Class S sites, must be in accordance with Table 4.2.13g and Figure 4.2.13.

Table 4.2.13a Stumps supporting single storey timber floor and metal roof

Floor load area (m2)

Dimension (mm)

Roof load area (m2)

0

6

12

3

Square pad footing size

250 x 250

300 x 300

350 x 350

8

Square pad footing size

400 x 400

400 x 400

450 x 450

12

Square pad footing size

450 x 450

500 x 500

500 x 500

3

Circular pad footing diameter

300

400

400

8

Circular pad footing diameter

450

450

600

12

Circular pad footing diameter

600

600

600

3

Pad footing depth

250

250

250

8

Pad footing depth

250

250

250

12

Pad footing depth

250

250

250

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.

Minimum bearing pressure is 100 kPa for pad footings.

For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.

Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of length/100 has been accounted for in the stumps.

A roof load area of “0” must be used for stumps not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 4.2.13b Stumps supporting single storey tiled floor and tiled roof

Floor load area (m2)

Dimension (mm)

Roof load area (m2)

0

6

12

3

Square pad footing size

300 x 300

400 x 400

450 x 450

8

Square pad footing size

450 x 450

500 x 500

550 x 500

12

Square pad footing size

500 x 500

550 x 550

600 x 600

3

Circular pad footing diameter

400

450

600

8

Circular pad footing diameter

600

600

650

12

Circular pad footing diameter

650

650

700

3

Pad footing depth

250

250

250

8

Pad footing depth

250

250

250

12

Pad footing depth

250

300

300

Table Notes

Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.

Minimum bearing pressure is 100 kPa for pad footings.

For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.

Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of length/100 has been accounted for in the stumps.

A roof load area of “0” must be used for stumps not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 4.2.13c Stumps supporting double storey timber floor and metal roof

Floor load area (m2)

Dimension (mm)

Roof load area (m2)

0

6

12

3

Square pad footing size

350 x 350

400 x 400

450 x 450

8

Square pad footing size

550 x 550

550 x 550

600 x 600

12

Square pad footing size

650 x 650

650 x 650

700 x 700

3

Circular pad footing diameter

400

450

600

8

Circular pad footing diameter

650

650

700

12

Circular pad footing diameter

750

750

800

3

Pad footing depth

250

250

250

8

Pad footing depth

300

300

350

12

Pad footing depth

350

350

350

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.

Minimum bearing pressure is 100 kPa for pad footings.

For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.

Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of length/100 has been accounted for in the stumps.

A roof load area of “0” must be used for stumps not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 4.2.13d Maximum stump height (mm): stump supporting single storey timber floor and metal roof

Stump material

Section size (mm)

Floor load area (m2)

Roof load area (m2)

0

6

12

Concrete f’c= 20 MPa

100 x 100

3

2500

2000

1750

Concrete f’c = 20 MPa

100 x 100

8

1500

1500

1500

Concrete f’c = 20 MPa

100 x 100

12

1250

1250

1250

Steel fy = 350 MPa

100 x 100 x 2.0

3

3000

3000

3000

Steel fy = 350 MPa

100 x 100 x 2.0

8

3000

3000

3000

Steel fy = 350 MPa

100 x 100 x 2.0

12

3000

3000

3000

Timber F17

100 x 100

3

3000

3000

3000

Timber F17

100 x 100

8

2500

2500

2250

Timber F17

100 x 100

12

2250

2000

2000

Timber F14

100 x 100

3

3000

3000

2500

Timber F14

100 x 100

8

2250

2000

1750

Timber F14

100 x 100

12

1750

1500

1500

Timber F11

100 x 100

3

3000

2500

2250

Timber F11

100 x 100

8

2000

1750

1750

Timber F11

100 x 100

12

1500

1500

1250

Timber F8

100 x 100

3

3000

2500

2000

Timber F8

100 x 100

8

1750

1500

1250

Timber F8

100 x 100

12

1250

1000

750

Timber F7

100 x 100

3

2500

2250

1750

Timber F7

100 x 100

8

1500

1250

750

Timber F7

100 x 100

12

750

–

–

Timber F5

100 x 100

3

2500

2000

1500

Timber F5

100 x 100

8

1250

750

–

Timber F5

100 x 100

12

–

–

–

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.

Minimum bearing pressure is 100 kPa for pad footings.

Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of length/100 has been accounted for in the stumps.

A roof load area of “0” must be used for stumps not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table 4.2.13e Maximum stump height: stump supporting single storey tiled floor and tiled roof

Stump material

Section size (mm)

Floor load area (m2)

Roof load area (m2)

0

6

12

Concrete f’c = 20 MPa

100 x 100

3

2250

1750

1500

Concrete f’c = 20 MPa

100 x 100

8

1500

1250

1250

Concrete f’c = 20 MPa

100 x 100

12

1250

1250

750

Steel fy = 350 MPa

100 x 100 x 2.0

3

3000

3000

3000

Steel fy = 350 MPa

100 x 100 x 2.0

8

3000

3000

3000

Steel fy = 350 MPa

100 x 100 x 2.0

12

3000

3000

3000

Timber F17

100 x 100

3

3000

3000

2500

Timber F17

100 x 100

8

2500

2250

2000

Timber F17

100 x 100

12

2000

2000

1750

Timber F14

100 x 100

3

3000

2500

2000

Timber F14

100 x 100

8

2000

1750

1500

Timber F14

100 x 100

Tables

Changed in NCC 2025. See ABCB Housing Provisions 2025 4.2.13, or show what changed.

(1) Footings for stumps must comply with — the provisions … is equal to the square root of the floor area. Concrete stumps with a height of 1400 mm or less must be reinforced with at least 1 5 mm hard drawn wire. Concrete stumps with a height greater than 1400 mm must be reinforced with at least 2 5 mm hard drawn wires. Table 4.2.13e Maximum stump height: stump supporting single storey tiled … 350 MPa 100 x 100 x 2.0 12 3000 3000 3000 Timber F17 100 x 100 3 3000 3000 2500 Timber F17 100 x 100 8 2500 2250 2000 Timber F17 100 x 100 12 2000 2000 1750 Timber F14 100 x 100 3 3000 2500 2000 Timber F14 100 x 100 8 2000 1750 1500 Timber F14 100 x 100