4.2.13 Stump footing details
Part 4.2 Footings, slabs and associated elements · NCC 2019: 3.2.5.6
(1) Footings for stumps must comply with—
the provisions of Tables 4.2.13a, 4.2.13b or 4.2.13c for Class A and Class S sites; or
the appropriate referenced document listed in—
H1D6(3); or
H1D4.
(2) Concrete stumps must—
be designed in accordance with—
AS 3600; or
Tables 4.2.13d, 4.2.13e or 4.2.13f; and
use a minimum 20 MPa concrete as defined in AS 3600.
(3) Steel stumps must be—
designed in accordance with—
AS 4100; or
Tables 4.2.13d, 4.2.13e or 4.2.13f; and
fully enclosed and sealed with a welded top plate; and
encased in concrete sloping away from the stump and finishing not less than 100 mm above finished ground level; and
corrosion protected in accordance with Part 6.3.
(4) Timber stumps must be designed in accordance with—
AS 1684.2, AS 1684.3, AS 1684.4 or AS 1720.1; or
Tables 4.2.13d, 4.2.13e or 4.2.13f.
(5) Stumps must be braced—
by a full perimeter masonry base; or
for concrete stumps — in accordance with AS 3600; or
for steel stumps — in accordance with AS 4100; or
for timber stumps — in accordance with AS 1684.2, AS 1684.3, AS 1684.4 or AS 1720.1.
(6) Stumps must be embedded into the foundation material not less than 30% of their height above ground level or 450 mm, whichever is the greater.
(7) Pad footings for clad frame, Class A and Class S sites, must be in accordance with Table 4.2.13g and Figure 4.2.13.
Table 4.2.13a Stumps supporting single storey timber floor and metal roof
Floor load area (m2)
Dimension (mm)
Roof load area (m2)
0
6
12
3
Square pad footing size
250 x 250
300 x 300
350 x 350
8
Square pad footing size
400 x 400
400 x 400
450 x 450
12
Square pad footing size
450 x 450
500 x 500
500 x 500
3
Circular pad footing diameter
300
400
400
8
Circular pad footing diameter
450
450
600
12
Circular pad footing diameter
600
600
600
3
Pad footing depth
250
250
250
8
Pad footing depth
250
250
250
12
Pad footing depth
250
250
250
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.
Minimum bearing pressure is 100 kPa for pad footings.
For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.
Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of length/100 has been accounted for in the stumps.
A roof load area of “0” must be used for stumps not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 4.2.13b Stumps supporting single storey tiled floor and tiled roof
Floor load area (m2)
Dimension (mm)
Roof load area (m2)
0
6
12
3
Square pad footing size
300 x 300
400 x 400
450 x 450
8
Square pad footing size
450 x 450
500 x 500
550 x 500
12
Square pad footing size
500 x 500
550 x 550
600 x 600
3
Circular pad footing diameter
400
450
600
8
Circular pad footing diameter
600
600
650
12
Circular pad footing diameter
650
650
700
3
Pad footing depth
250
250
250
8
Pad footing depth
250
250
250
12
Pad footing depth
250
300
300
Table Notes
Load accounted for includes 0.98 kPa permanent floor, 0.92 kN/m permanent wall, 0.85 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.
Minimum bearing pressure is 100 kPa for pad footings.
For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.
Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of length/100 has been accounted for in the stumps.
A roof load area of “0” must be used for stumps not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 4.2.13c Stumps supporting double storey timber floor and metal roof
Floor load area (m2)
Dimension (mm)
Roof load area (m2)
0
6
12
3
Square pad footing size
350 x 350
400 x 400
450 x 450
8
Square pad footing size
550 x 550
550 x 550
600 x 600
12
Square pad footing size
650 x 650
650 x 650
700 x 700
3
Circular pad footing diameter
400
450
600
8
Circular pad footing diameter
650
650
700
12
Circular pad footing diameter
750
750
800
3
Pad footing depth
250
250
250
8
Pad footing depth
300
300
350
12
Pad footing depth
350
350
350
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.
Minimum bearing pressure is 100 kPa for pad footings.
For pad footings founded on rock, the width or diameter may be reduced by half but not less than 250 mm x 250 mm or 300 mm diameter.
Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of length/100 has been accounted for in the stumps.
A roof load area of “0” must be used for stumps not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 4.2.13d Maximum stump height (mm): stump supporting single storey timber floor and metal roof
Stump material
Section size (mm)
Floor load area (m2)
Roof load area (m2)
0
6
12
Concrete f’c= 20 MPa
100 x 100
3
2500
2000
1750
Concrete f’c = 20 MPa
100 x 100
8
1500
1500
1500
Concrete f’c = 20 MPa
100 x 100
12
1250
1250
1250
Steel fy = 350 MPa
100 x 100 x 2.0
3
3000
3000
3000
Steel fy = 350 MPa
100 x 100 x 2.0
8
3000
3000
3000
Steel fy = 350 MPa
100 x 100 x 2.0
12
3000
3000
3000
Timber F17
100 x 100
3
3000
3000
3000
Timber F17
100 x 100
8
2500
2500
2250
Timber F17
100 x 100
12
2250
2000
2000
Timber F14
100 x 100
3
3000
3000
2500
Timber F14
100 x 100
8
2250
2000
1750
Timber F14
100 x 100
12
1750
1500
1500
Timber F11
100 x 100
3
3000
2500
2250
Timber F11
100 x 100
8
2000
1750
1750
Timber F11
100 x 100
12
1500
1500
1250
Timber F8
100 x 100
3
3000
2500
2000
Timber F8
100 x 100
8
1750
1500
1250
Timber F8
100 x 100
12
1250
1000
750
Timber F7
100 x 100
3
2500
2250
1750
Timber F7
100 x 100
8
1500
1250
750
Timber F7
100 x 100
12
750
–
–
Timber F5
100 x 100
3
2500
2000
1500
Timber F5
100 x 100
8
1250
750
–
Timber F5
100 x 100
12
–
–
–
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.
Minimum bearing pressure is 100 kPa for pad footings.
Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of length/100 has been accounted for in the stumps.
A roof load area of “0” must be used for stumps not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table 4.2.13e Maximum stump height: stump supporting single storey tiled floor and tiled roof
Stump material
Section size (mm)
Floor load area (m2)
Roof load area (m2)
0
6
12
Concrete f’c = 20 MPa
100 x 100
3
2250
1750
1500
Concrete f’c = 20 MPa
100 x 100
8
1500
1250
1250
Concrete f’c = 20 MPa
100 x 100
12
1250
1250
750
Steel fy = 350 MPa
100 x 100 x 2.0
3
3000
3000
3000
Steel fy = 350 MPa
100 x 100 x 2.0
8
3000
3000
3000
Steel fy = 350 MPa
100 x 100 x 2.0
12
3000
3000
3000
Timber F17
100 x 100
3
3000
3000
2500
Timber F17
100 x 100
8
2500
2250
2000
Timber F17
100 x 100
12
2000
2000
1750
Timber F14
100 x 100
3
3000
2500
2000
Timber F14
100 x 100
8
2000
1750
1500
Timber F14
100 x 100
Tables
- Table 4.2.13a Stumps supporting single storey timber floor and metal roof
- Table 4.2.13b Stumps supporting single storey tiled floor and tiled roof
- Table 4.2.13c Stumps supporting double storey timber floor and metal roof
- Table 4.2.13d Maximum stump height (mm): stump supporting single storey timber floor and metal roof
- Table 4.2.13e Maximum stump height: stump supporting single storey tiled floor and tiled roof
- Table 4.2.13f Maximum stump height: stump supporting double storey timber floor and metal roof
- Table 4.2.13g Minimum dimensions of circular and square pad footings for clad frame, Class A and S sites
Changed in NCC 2025. See ABCB Housing Provisions 2025 4.2.13, or show what changed.
(1) Footings for stumps must comply with — the provisions … is equal to the square root of the floor area. Concrete stumps with a height of 1400 mm or less must be reinforced with at least 1 5 mm hard drawn wire. Concrete stumps with a height greater than 1400 mm must be reinforced with at least 2 5 mm hard drawn wires. Table 4.2.13e Maximum stump height: stump supporting single storey tiled … 350 MPa 100 x 100 x 2.0 12 3000 3000 3000 Timber F17 100 x 100 3 3000 3000 2500 Timber F17 100 x 100 8 2500 2250 2000 Timber F17 100 x 100 12 2000 2000 1750 Timber F14 100 x 100 3 3000 2500 2000 Timber F14 100 x 100 8 2000 1750 1500 Timber F14 100 x 100