Table 4.2.13d Maximum stump height (mm): stump supporting single storey timber floor and metal roof
Part 4.2 Footings, slabs and associated elements
| Stump material | Section size (mm) | Floor load area (m2) | Roof load area (m2) | ||
|---|---|---|---|---|---|
| 0 | 6 | 12 | |||
| Concrete f’c= 20 MPa | 100 x 100 | 3 | 2500 | 2000 | 1750 |
| Concrete f’c = 20 MPa | 100 x 100 | 8 | 1500 | 1500 | 1500 |
| Concrete f’c = 20 MPa | 100 x 100 | 12 | 1250 | 1250 | 1250 |
| Steel fy = 350 MPa | 100 x 100 x 2.0 | 3 | 3000 | 3000 | 3000 |
| Steel fy = 350 MPa | 100 x 100 x 2.0 | 8 | 3000 | 3000 | 3000 |
| Steel fy = 350 MPa | 100 x 100 x 2.0 | 12 | 3000 | 3000 | 3000 |
| Timber F17 | 100 x 100 | 3 | 3000 | 3000 | 3000 |
| Timber F17 | 100 x 100 | 8 | 2500 | 2500 | 2250 |
| Timber F17 | 100 x 100 | 12 | 2250 | 2000 | 2000 |
| Timber F14 | 100 x 100 | 3 | 3000 | 3000 | 2500 |
| Timber F14 | 100 x 100 | 8 | 2250 | 2000 | 1750 |
| Timber F14 | 100 x 100 | 12 | 1750 | 1500 | 1500 |
| Timber F11 | 100 x 100 | 3 | 3000 | 2500 | 2250 |
| Timber F11 | 100 x 100 | 8 | 2000 | 1750 | 1750 |
| Timber F11 | 100 x 100 | 12 | 1500 | 1500 | 1250 |
| Timber F8 | 100 x 100 | 3 | 3000 | 2500 | 2000 |
| Timber F8 | 100 x 100 | 8 | 1750 | 1500 | 1250 |
| Timber F8 | 100 x 100 | 12 | 1250 | 1000 | 750 |
| Timber F7 | 100 x 100 | 3 | 2500 | 2250 | 1750 |
| Timber F7 | 100 x 100 | 8 | 1500 | 1250 | 750 |
| Timber F7 | 100 x 100 | 12 | 750 | – | – |
| Timber F5 | 100 x 100 | 3 | 2500 | 2000 | 1500 |
| Timber F5 | 100 x 100 | 8 | 1250 | 750 | – |
| Timber F5 | 100 x 100 | 12 | – | – | – |
Table Notes
Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.
Minimum bearing pressure is 100 kPa for pad footings.
Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.
A maximum load eccentricity of length/100 has been accounted for in the stumps.
A roof load area of “0” must be used for stumps not supporting roof loads.
The length of wall load allowed for is equal to the square root of the floor area.
Table for 4.2.13 Stump footing details
Changed in NCC 2025. See ABCB Housing Provisions 2025 Table 4.2.13d, or show what changed.
Stump material | Section size (mm) | Floor load area … is equal to the square root of the floor area. Concrete stumps with a height of 1400 mm or less must be reinforced with at least 1 5 mm hard drawn wire. Concrete stumps with a height greater than 1400 mm must be reinforced with at least 2 5 mm hard drawn wires.
Removed words are struck through; added words are highlighted. Comparison of the text only.