Table · ABCB Housing Provisions 2022

Table 4.2.13f Maximum stump height: stump supporting double storey timber floor and metal roof

Part 4.2 Footings, slabs and associated elements

Open Table 4.2.13f on NCC Online ↗
Stump materialSection size (mm)Floor load area (m2)Roof load area (m2)
0612
Concrete f’c = 20 MPa100 x 1003175015001500
Concrete f’c = 20 MPa100 x 100812501000750
Concrete f’c = 20 MPa100 x 10012–––
Steel fy = 350 MPa100 x 100 x 2.03300030003000
Steel fy = 350 MPa100 x 100 x 2.08300030003000
Steel fy = 350 MPa100 x 100 x 2.012300027502500
Timber F17100 x 1003300025002500
Timber F17100 x 1008175017501500
Timber F17100 x 10012125012501250
Timber F14100 x 1003250022502000
Timber F14100 x 1008125012501000
Timber F14100 x 10012750500500
Timber F11100 x 1003225020001750
Timber F11100 x 100810001000750
Timber F11100 x 10012–––
Timber F8100 x 1003200017501500
Timber F8100 x 1008500500–
Timber F8100 x 10012–––
Timber F7100 x 1003175015001250
Timber F7100 x 1008–––
Timber F7100 x 10012–––
Timber F5100 x 100315001000750
Timber F5100 x 1008–––
Timber F5100 x 10012–––

Table Notes

Load accounted for includes 0.53 kPa permanent floor, 0.92 kN/m permanent wall, 0.4 kPa permanent roof, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations for ULS included are 1.35G and 1.2G + 1.5Q for stumps and G + 0.5Q for pad footings.

Minimum bearing pressure is 100 kPa for pad footings.

Stumps are assumed to be braced and simply-supported at both ends with an effective length factor of 1.

A maximum load eccentricity of length/100 has been accounted for in the stumps.

A roof load area of “0” must be used for stumps not supporting roof loads.

The length of wall load allowed for is equal to the square root of the floor area.

Table for 4.2.13 Stump footing details

Changed in NCC 2025. See ABCB Housing Provisions 2025 Table 4.2.13f, or show what changed.

Stump material | Section size (mm) | Floor load area … is equal to the square root of the floor area. Concrete stumps with a height of 1400 mm or less must be reinforced with at least 1 5 mm hard drawn wire. Concrete stumps with a height greater than 1400 mm must be reinforced with at least 2 5 mm hard drawn wires.