Table 4.2.20f Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 18 m2
Part 4.2 Footings, slabs and associated elements
| Localised thickening | Maximum floor load area (m2) | ||
|---|---|---|---|
| 4 | 10 | 16 | |
| Square thickening size (mm) | 600 x 600 | 750 x 750 | 850 x 850 |
| Thickening depth (mm) | 300 | 400 | 450 |
Table Notes
Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.
Load combinations included are G + 0.5Q for ULS.
Minimum bearing pressure is 1000 kPa for pad footings.
The length of wall allowed for is equal to the square root of the floor area.
Table for 4.2.20 Concentrated loads
Changed in NCC 2025 (minor wording). See ABCB Housing Provisions 2025 Table 4.2.20f, or show what changed.