4.2.20 Concentrated loads

Part 4.2 Footings, slabs and associated elements

Open 4.2.20 on NCC Online ↗

Where a footing or slab supports a concentrated load from a structural steel column, localised thickening must—

be provided in accordance with—

for tiled floor and tiled roof, Tables 4.2.20a, 4.2.20b or 4.2.20c; or

for timber floor and metal roof, Tables 4.2.20d, 4.2.20e or 4.2.20f; and

be centred under the structural steel column; and

have SL72 reinforcement with a minimum 50 mm of concrete cover (see Figure 4.2.20).

Table 4.2.20a Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = 0 m2

Localised thickening

Maximum floor load area (m2)

4

10

16

Square thickening size (mm)

450 x 450

650 x 650

850 x 850

Thickening depth (mm)

250

350

400

Table Notes

Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 100 kPa for pad footings.

A roof load area of “0” must be used for footings not supporting roof loads.

The length of wall allowed for is equal to the square root of the floor area.

Table 4.2.20b Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 9 m2

Localised thickening

Maximum floor load area (m2)

4

10

16

Square thickening size (mm)

650 x 650

800 x 800

950 x 950

Thickening depth (mm)

350

400

450

Table Notes

Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 1000 kPa for pad footings.

The length of wall allowed for is equal to the square root of the floor area.

Table 4.2.20c Localised thickening under concentrated load — tiled floor and tiled roof — roof load area = maximum 18 m2

Localised thickening

Maximum floor load area (m2)

4

10

16

Square thickening size (mm)

750 x 750

900 x 900

1000 x 1000

Thickening depth (mm)

400

450

500

Table Notes

Load accounted for includes 0.98 kPa permanent tiled floor, 0.85 kPa permanent tiled roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 1000 kPa for pad footings.

The length of wall allowed for is equal to the square root of the floor area.

Table 4.2.20d Localised thickening under concentrated load — timber floor and metal roof — roof load area = 0 m2

Localised thickening

Maximum floor load area (m2)

4

10

16

Square thickening size (mm)

400 x 400

600 x 600

750 x 750

Thickening depth (mm)

250

300

350

Table Notes

Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 1000 kPa for pad footings.

A roof load area of “0” must be used for footings not supporting roof loads.

The length of wall allowed for is equal to the square root of the floor area.

Table 4.2.20e Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 9 m2

Localised thickening

Maximum floor load area (m2)

4

10

16

Square thickening size (mm)

500 x 500

700 x 700

800 x 800

Thickening depth (mm)

300

350

400

Table Notes

Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 1000 kPa for pad footings.

The length of wall allowed for is equal to the square root of the floor area.

Table 4.2.20f Localised thickening under concentrated load — timber floor and metal roof — roof load area = maximum 18 m2

Localised thickening

Maximum floor load area (m2)

4

10

16

Square thickening size (mm)

600 x 600

750 x 750

850 x 850

Thickening depth (mm)

300

400

450

Table Notes

Load accounted for includes 0.53 kPa permanent timber floor, 0.4 kPa permanent metal roof, 1.16 kN/m permanent wall, permanent member self-weight, 1.5 kPa or 1.1 kN imposed floor and 0.25 kPa imposed roof.

Load combinations included are G + 0.5Q for ULS.

Minimum bearing pressure is 1000 kPa for pad footings.

The length of wall allowed for is equal to the square root of the floor area.

Figure 4.2.20 Localised thickening for concentrated loads

Tables

Changed in NCC 2025. See ABCB Housing Provisions 2025 4.2.20, or show what changed.

Where a footing or slab supports a concentrated load from … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. A roof load area of “0” … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … are G + 0.5Q for ULS. Minimum bearing pressure is 1000 100 kPa for pad footings. The length of wall allowed for … the floor area. Figure 4.2.20 Localised thickening for concentrated loads