B1P4 Buildings in flood areas
Part B1 Structural provisions · NCC 2019: BP1.4
(1) A building in a flood hazard area, must be designed and constructed, to the degree necessary, to resist flotation, collapse or significant permanent movement resulting from the action of hydrostatic, hydrodynamic, erosion and scour, wind and other actions during the defined flood event.
(2) The actions and requirements to be considered to satisfy (1) include but are not limited to—
flood actions; and
elevation requirements; and
foundation and footing requirements; and
requirements for enclosures below the flood hazard level; and
requirements for structural connections; and
material requirements; and
requirements for utilities; and
requirements for occupant egress.
Applications
B1P4 only applies to—
a Class 2 or 3 building or a Class 4 part of a building; and
a Class 9a health-care building; and
a Class 9c building.