Deemed-to-Satisfy Provision · NCC 2022 Volume One
D3D3 Fire-isolated stairways and ramps
Part D3 Construction of exits · NCC 2019: D2.2
A stairway or ramp (including any landings) that is required to be within a fire-resisting shaft must be constructed—
of non-combustible materials; and
so that if there is local failure it will not cause structural damage to, or impair the fire-resistance of, the shaft.