E2D17 Class 9b – assembly buildings: exhibition halls
Part E2 Smoke hazard management · NCC 2019: NSW Table E2.2b, Table E2.2b
A Class 9b assembly building which is an exhibition hall must be provided with—
automatic shutdown of any air-handling system (other than miscellaneous exhaust air systems installed in accordance with Sections 5 and 6 of AS 1668.1) which does not form part of the smoke hazard management system, on the activation of—
smoke detectors installed complying with Specification 20; and
any other installed fire detection and alarm system, including a sprinkler system complying with Specification 17; and
where the floor area is more than 2000 m2 and not more than 3500 m2—
an automatic smoke exhaust system complying with Specification 21; or
if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and
where the floor area is more than 3500 m2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and—
an automatic smoke exhaust system complying with Specification 21; or
automaticsmoke-and-heat vents complying with Specification 22, if the building is single storey.