NSW E2D17 Class 9b – assembly buildings: night clubs, discotheques and the like
Part E2 Smoke hazard management · varies E2D17 Class 9b – assembly buildings: exhibition halls
Delete clause E2D17 and insert NSW E2D17 as follows:
A building or part of a building being a night club, discotheque or the like, must be provided with—
in an auditorium—
an automatic smoke exhaust system complying with Specification 21; or
roof mounted automatic smoke-and-heat vents complying with Specification 22, in a single storey building or the top storey of a multi storey building; or
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 with fast response sprinkler heads; and
in all other areas—
where a building or part of a building has a floor area not more than 2000 m2—
one of the smoke hazard management measures listed under (a) above; or
an automatic smoke detection and alarm system complying with Specification 20; or
where a building or part of a building has a floor area of more than 2000 m2, smoke hazard management measures as provided for under NSW E2D19.
Notes
Paragraph (a) applies only to an auditorium designed principally to accommodate an audience to an entertainment.
Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.