E2D18 Class 9b – assembly buildings: theatres and public halls
Part E2 Smoke hazard management · NCC 2019: NSW Table E2.2b, Table E2.2b
(1) This clause applies to a Class 9b assembly building where the building or part of the building is used as a theatre or public hall which—
is a school assembly, church or community hall, and has a stage and any backstage area with a total floor area of more than 300 m2; or
is not a school assembly, church or community hall, and has a stage and any backstage area with a total floor area of more than 200 m2; or
has a stage with an associated rigging loft.
(2) A building or part of a building referred to in (1) must be provided with—
an automatic smoke exhaust system complying with Specification 21; or
if the building is single storey, automatic smoke-and-heat vents complying with Specification 22.