New South Wales variation · NCC 2022 Volume One

NSW E2D18 Class 9b – assembly buildings: exhibition halls, museums and art galleries

Part E2 Smoke hazard management · varies E2D18 Class 9b – assembly buildings: theatres and public halls

Open on NCC Online ↗

Delete clause E2D18 and insert NSW E2D18 as follows:

A building or part of a building used as an exhibition hall, museum, art gallery or the like, must be provided with—

where the floor area is more than 2000 m2 and not more than 3500 m2—

an automatic smoke exhaust system complying with Specification 21; or

roof mounted automatic smoke-and-heat vents complying with Specification 22 in a single storey building or the top storey of a multi storey building; or

a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17; and

where the floor area is more than 3500 m2, a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17 and—

an automatic smoke exhaust system complying with Specification 21; or

roof mounted automatic smoke-and-heat vents complying with Specification 22 , in a single storey building or the top storey of a multi storey building.

Notes

Smoke hazard management provisions for an assembly building used for multiple purposes must comply with all the relevant provisions of NSW E2D16, NSW E2D17, NSW E2D18 and NSW E2D19 according to usage.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One NSW E2D18.

The national clause