E2D20 Class 9b assembly buildings: other assembly buildings (not listed in E2D16 to E2D19)
Part E2 Smoke hazard management · NCC 2019: Table E2.2b
(1) The requirements of (2)—
apply to a Class 9b assembly building where the building or part of the building is used for a purpose other than—
as described in E2D16 to E2D19; or
a school; and
do not apply to—
sporting complexes (including sports halls, gymnasiums, swimming pools, ice and roller rinks, and the like) other than an indoor sports stadium with total spectator seating for more than 1000; or
churches and other places used solely for religious worship.
(2) Each fire compartment, other than one in a building referred to in (1)(b), where the floor area of the Class 9b part is more than 2000 m2 must be provided with—
an automatic smoke exhaust system complying with Specification 21; or
if the building is single storey, automatic smoke-and-heat vents complying with Specification 22; or
if the floor area of the fire compartment is not more than 5000 m2 and the building has a rise in storeys of not more than 2—
an automatic smoke detection and alarm system complying with Specification 20; or
a sprinkler system (other than a FPAA101D or FPAA101H system) complying with Specification 17.
(3) A building containing a Class 9b early childhood centre must be provided with an automatic smoke detection and alarm system complying with Specification 20 throughout the whole building, including any part of another class.
Changed since NCC 2022. See NCC 2022 Volume One E2D20, or show what changed.
(1) The requirements of (2)— apply to a Class 9b … other than one in a building referred to in (1)(b), having a where the floor area of the Class 9b part is more than 2000 m2 must be provided with — an … throughout the whole building, including any part of another class.
Removed words are struck through; added words are highlighted. Comparison of the text only.
State and territory variations all clauses side by side →
Clauses referred to
- E2D16 Class 9b – assembly buildings: nightclubs, discotheques and the like
- E2D19 Class 9b – assembly buildings: theatres and public halls (not listed in E2D18) including lecture theatres and cinema/auditorium complexes