Deemed-to-Satisfy Provision · NCC 2022 Volume One

E2D4 Fire-isolated exits

Part E2 Smoke hazard management · NCC 2019: Table E2.2a

Open E2D4 on NCC Online ↗

(1) A part of a building listed in (2) must be provided with—

an automatic air pressurisation system for fire-isolated exits in accordance with AS 1668.1; or

open access ramps or balconies in accordance with D3D6.

(2) The requirements of (1) apply to—

a required fire-isolated stairway, including any associated fire-isolated passageway or fire-isolated ramp serving—

any storey above an effective height of 25 m; or

more than 2 below ground storeys, not counted in the rise in storeys in accordance with C2D3; or

an atrium to which Part G3 applies; or

a Class 9a building with a rise in storeys of more than 2; or

a Class 9c building with a rise in storeys of more than 2; or

a Class 3 building used as a residential care building with a rise in storeys of more than 2; and

a required fire-isolated passageway or fire-isolated ramp with a length of travel more than 60 m to a road or open space.

(3) An automatic air pressurisation system for a fire-isolated exit must serve the entire exit.

Notes

Refer to D2D12(4) for pressurisation of a fire-isolated exit having more than 2 access doorways from within the same storey.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E2D4.
Can't meet E2D4? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →