E2D4 Fire-isolated exits
Part E2 Smoke hazard management · NCC 2019: Table E2.2a
(1) A part of a building listed in (2) must be provided with—
an automatic air pressurisation system for fire-isolated exits in accordance with AS 1668.1; or
open access ramps or balconies in accordance with D3D6.
(2) The requirements of (1) apply to—
a required fire-isolated stairway, including any associated fire-isolated passageway or fire-isolated ramp serving—
any storey above an effective height of 25 m; or
more than 2 below ground storeys, not counted in the rise in storeys in accordance with C2D3; or
an atrium to which Part G3 applies; or
a Class 9a building with a rise in storeys of more than 2; or
a Class 9c building with a rise in storeys of more than 2; or
a Class 3 building used as a residential care building with a rise in storeys of more than 2; and
a required fire-isolated passageway or fire-isolated ramp with a length of travel more than 60 m to a road or open space.
(3) An automatic air pressurisation system for a fire-isolated exit must serve the entire exit.
Notes
Refer to D2D12(4) for pressurisation of a fire-isolated exit having more than 2 access doorways from within the same storey.
Clauses referred to
- D3D6 Open access ramps and balconies
- C2D3 Calculation of rise in storeys