E2D5 Buildings more than 25 m in effective height: Class 2 and 3 buildings and Class 4 part of a building

Part E2 Smoke hazard management · NCC 2019: Table E2.2a

Open E2D5 on NCC Online ↗

An automatic smoke detection and alarm system complying with Specification 20 must be provided to the following:

A Class 2 or 3 building which is more than 25 m in effective height.

A Class 2 or 3 part of a building, or a Class 4 part of a building, in a building which is more than 25 m in effective height.

Notes

Refer to C3D15 for division of public corridors greater than 40 m in length.

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One E2D5.
Can't meet E2D5? A Performance Solution must meet the Performance Requirements it satisfies: E2P1, E2P2. Start a Performance Solution →