Deemed-to-Satisfy Provision · NCC 2025 Volume One

F4D7 Accessible unisex showers

Part F4 Sanitary and other facilities · NCC 2019: Table F2.4b

Open F4D7 on NCC Online ↗
Varied in SA. Check the variation for your state.

(1) Where required by F4D5(b), the minimum number of accessible unisex showers for each class of building is as follows:

For a Class 1b building—

not less than 1; and

where private accessible unisex showers are provided for every accessible bedroom, common accessible unisex showers need not be provided.

For a Class 2 building, where showers are provided in common areas, not less than 1.

For Class 3 and 9c buildings—

in every accessible sole-occupancy unit provided with showers within the accessible sole-occupancy unit, not less than 1; and

1 for every 10 showers or part thereof provided in common areas.

For Class 5, 6, 7, 8 or 9 buildings, where F4D4 requires 1 or more showers, not less than 1 for every 10 showers or part thereof.

For a Class 10a building, where showers are provided, 1 for every 10 showers or part thereof.

(2) The requirements of (1)(d) do not apply within a ward area of a Class 9a health-care building.

(3) The requirements of (1)(e) do not apply to—

a Class 10a appurtenant to another class of building; and

a sanitary compartment dedicated to a single caravan/camping site.

Same wording in NCC 2022 Volume One. See NCC 2022 Volume One F4D7.
Can't meet F4D7? A Performance Solution must meet the Performance Requirements it satisfies: F4P1, F4P2, F4P3, F4P4, F4P5, F4P6. Start a Performance Solution →

State and territory variations all clauses side by side →