Verification Method · NCC 2022 Volume One

F7V3 Sound transmission through floors [F7P3]

Part F7 Sound transmission and insulation · NCC 2019: FV5.3

Open F7V3 on NCC Online ↗

Compliance with F7P3 to avoid the transmission of airborne and impact generated sound through floors is verified when it is measured in-situ that the separating floor has—

airborne: a weighted standardised level difference (DnT,w) not less than 40 when determined under AS/NZS ISO 717.1; and

impact: a weighted standardised impact sound pressure level (LnT,w) not more than 62 when determined under AS ISO 717.2.

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One F7V3, or show what changed.

Compliance with F7P3 to avoid the transmission of airborne and … level difference (DnT,w) not less than 40 when determined under AS/NZS AS ISO 717.1; and impact: a weighted standardised impact sound pressure level (LnT,w) not more than 62 when determined under AS ISO 717.2.