Deemed-to-Satisfy Provision · NCC 2022 Volume One

F8D4 Exhaust systems

Part F8 Condensation management · NCC 2019: F6.3

Open F8D4 on NCC Online ↗

(1) An exhaust system installed in a kitchen, bathroom, sanitary compartment or laundry must have a minimum flow rate of—

25 L/s for a bathroom or sanitary compartment; and

40 L/s for a kitchen or laundry.

(2) Exhaust from a kitchen, kitchen range hood, bathroom, sanitary compartment or laundry must discharge directly or via a shaft or duct to outdoor air.

(3) Where space for a clothes drying appliance is provided in accordance with F4D2(1)(b), space must also be provided for ducting from the clothes drying appliance to outdoor air.

(4) (3) does not apply if a condensing-type clothes drying appliance is installed.

(5) An exhaust system that is not run continuously and is serving a bathroom or sanitary compartment that is not ventilated in accordance with F6D7 must—

be interlocked with the room’s light switch; and

include a run-on timer so that the exhaust system continues to operate for 10 minutes after the light switch is turned off.

(6) Except for rooms that are ventilated in accordance with F6D7, a room with space for ducting a clothes drying appliance to outdoor air in accordance with (3) must be provided with make-up air in accordance with AS 1668.2

Changed in NCC 2025 (minor wording). See NCC 2025 Volume One F8D4, or show what changed.

(1) An exhaust system installed in a kitchen, bathroom, sanitary … must be provided with make-up air in accordance with AS 1668.2 1668.2.

Removed words are struck through; added words are highlighted. Comparison of the text only.

Can't meet F8D4? A Performance Solution must meet the Performance Requirements it satisfies: F8P1. Start a Performance Solution →

Clauses referred to

Defined terms used