Deemed-to-Satisfy Provision · NCC 2022 Volume One

J3D4 Ceiling fans in a sole-occupancy unit of a Class 2 building or a Class 4 part of a building

Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building · NCC 2019: J0.3

Open J3D4 on NCC Online ↗
Varied in NSW. Check the variation for your state.

(1) Ceiling fans must be installed in accordance with Table J3D4 in—

climate zones 1, 2 and 3; and

climate zone 5 in New South Wales and Queensland.

(2) Ceiling fans required by (1) must—

be permanently installed; and

have a speed controller.

Table J3D4 Minimum ceiling fan requirements in climate zones 1, 2, 3 and 5

Size of room (m2)

Minimum number and diameter (mm) of ceiling fans required for a bedroom in climate zones 1, 2 and 3

Minimum number and diameter (mm) of ceiling fans required in a habitable room other than a bedroom in climate zones 1, 2, 3 and 5 (NSW and Qld)

< 15

1 x 900

1 x 900

≥ 15 to < 20

1 x 1200

1 x 1200

≥ 20 to < 25

1 x 1200

1 x 1400

≥ 25 to < 30

1 x 1400

2 x 1200

≥ 30 to < 45

1 x 1400

2 x 1400

≥ 45 to < 50

2 x 1400

3 x 1200

≥ 50

2 x 1400

3 x 1400

Tables

Same wording in NCC 2025 Volume One. See NCC 2025 Volume One J3D4.
Can't meet J3D4? A Performance Solution must meet the Performance Requirements it satisfies: J1P1, J1P2, J1P3, J1P4. Start a Performance Solution →

State and territory variations all clauses side by side →