J3D4 Ceiling fans in a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
Part J3 Elemental provisions for a sole-occupancy unit of a Class 2 building or a Class 4 part of a building · NCC 2019: J0.3
(1) Ceiling fans must be installed in accordance with Table J3D4 in—
climate zones 1, 2 and 3; and
climate zone 5 in New South Wales and Queensland.
(2) Ceiling fans required by (1) must—
be permanently installed; and
have a speed controller.
Table J3D4 Minimum ceiling fan requirements in climate zones 1, 2, 3 and 5
Size of room (m2)
Minimum number and diameter (mm) of ceiling fans required for a bedroom in climate zones 1, 2 and 3
Minimum number and diameter (mm) of ceiling fans required in a habitable room other than a bedroom in climate zones 1, 2, 3 and 5 (NSW and Qld)
< 15
1 x 900
1 x 900
≥ 15 to < 20
1 x 1200
1 x 1200
≥ 20 to < 25
1 x 1200
1 x 1400
≥ 25 to < 30
1 x 1400
2 x 1200
≥ 30 to < 45
1 x 1400
2 x 1400
≥ 45 to < 50
2 x 1400
3 x 1200
≥ 50
2 x 1400
3 x 1400