Table · NCC 2022 Volume One
Table J3D4 Minimum ceiling fan requirements in climate zones 1, 2, 3 and 5
| Size of room (m2) | Minimum number and diameter (mm) of ceiling fans required for a bedroom in climate zones 1, 2 and 3 | Minimum number and diameter (mm) of ceiling fans required in a habitable room other than a bedroom in climate zones 1, 2, 3 and 5 (NSW and Qld) |
|---|---|---|
| < 15 | 1 x 900 | 1 x 900 |
| ≥ 15 to < 20 | 1 x 1200 | 1 x 1200 |
| ≥ 20 to < 25 | 1 x 1200 | 1 x 1400 |
| ≥ 25 to < 30 | 1 x 1400 | 2 x 1200 |
| ≥ 30 to < 45 | 1 x 1400 | 2 x 1400 |
| ≥ 45 to < 50 | 2 x 1400 | 3 x 1200 |
| ≥ 50 | 2 x 1400 | 3 x 1400 |
Table for J3D4 Ceiling fans in a sole-occupancy unit of a Class 2 building or a Class 4 part of a building
Same wording in NCC 2025 Volume One. See NCC 2025 Volume One Table J3D4.